Delta DVP06AD-S

Delta DVP06AD-S – 6-channel analog input module

Delta DVP06AD-S converts six voltage or current inputs into digital values for the PLC. It is part of the DVP Slim analog module range and has zero analog outputs. Typical signals include pressure, level and position measurements. Delta’s instruction sheet lists DVP-SS, DVP-SA, DVP-SX, DVP-SC and DVP-SV CPUs. Check the full CPU model and its expansion connection.

Supply, input ranges and wiring

The module uses 24 V DC power with a specified range of 20.4–28.8 V DC. Conversion takes 3 ms per channel. Hardware resolution is 14 bits for voltage and 13 bits for current. Read measurements as signed 16-bit values. Analog and digital circuits are isolated from each other. The analog channels share a common reference.

CR#1 selects the mode separately for each channel. Mode 0 is −10 to +10 V, Mode 1 is −6 to +10 V, Mode 2 is −12 to +20 mA and Mode 3 is −20 to +20 mA. The factory setting is Mode 0 for all six channels. For voltage, use the channel’s V+ and COM. For current, bridge V+ and I+ on the same channel and return to COM. Complete a two-wire transmitter loop according to its own supply diagram.

4–20 mA scaling example. With factory OFFSET/GAIN in Mode 2, 4 mA → 0, 12 mA → 2000 and 20 mA → 4000. For a 0–10 bar transmitter, a raw value of 2000 represents about 5 bar. In Mode 3, 4 mA produces about 800 counts. Scale the PLC or HMI using the curve for the selected mode.

PLC registers and Modbus addresses

Over the CPU expansion bus, use TO to set channel parameters and FROM to read values. CR#6–CR#11 hold CH1–CH6 averages. CR#12–CR#17 hold present values. CR#2–CR#4 set the averaging sample count for two channels per word. CR#30 reports error status.

For module number 0, FROM K0 K12 D100 K6 reads the six present values into D100–D105. The first K0 refers to the module nearest the CPU. Adjust it to match the actual installation order.

Delta’s instruction sheet specifies disconnecting the module from the CPU expansion bus when using its own RS-485 port. CH1 average is at 0x4006 and CH1 present value is at 0x400C. Read CH1–CH6 present values at 0x400C–0x4011 with function 03. Write mode settings to CR#1 / 0x4001 with single-register function 06. Measurement registers are read-only. If the client uses one-based decimal addressing, CH1 present value is 16397. Match the serial format and station address on both devices.

Programming software and cable

Download the PLC program to the host CPU. Choose a version of WPLSoft or ISPSoft that supports that CPU. In ISPSoft, COMMGR can manage the connection profile. The UC-PRG020-12A USB-to-RS-232 cable is an option for a compatible COM1 RS-232 port. See DVP programming cables for CPU connections and DVP communication cables for field communication options.

Related topics

For four analog inputs, see DVP04AD-S and DVP04AD-S2. For different speed requirements, compare DVP06AD-SH and DVP04AD-SL. For mixed analog inputs and outputs, see DVP06XA-S and DVP06XA-S2.

Analog output options include DVP02DA-S, DVP04DA-S, DVP04DA-S2 and DVP04DA-SL. Check signal direction, terminal layout and register assignments before replacing a module.

Editor’s Note

For a used unit, check the exact AD-S suffix and confirm that the removable terminal block is present.

Test all six channels individually with a calibrator. For a 4–20 mA loop, record raw values at 4, 12 and 20 mA.

If the current source is correct and the channel stays flat, check the V+/I+ bridge, the COM return and the CR#1 mode first.

If a value fluctuates, separate the analog cable from drive output wiring. Measure the signal before adjusting the filter.

Compare a suspect channel with a working one using the same source. Record the existing OFFSET and GAIN settings before changing them.

PDF documents and navigation

Delta DVP PLC PDF files · DVP expansion modules · DVP PLC series · Delta PLC · Delta main page

External references · DVP06AD-S installation and CR sheet (EN/Chinese) · DVP Module Manual, chapter 8 (EN)