Delta DVP06AD-SH
Delta DVP06AD-SH – 6-Channel Analogue Input Module
Delta DVP06AD-SH is a special expansion module in the Delta DVP Slim PLC family. Delta’s declaration of conformity lists it with six analogue inputs, zero analogue outputs and a DC supply classification. The analogue inputs pass field measurements to the PLC program as numeric values. The difference between analogue and digital inputs matters when the program needs the magnitude of a measurement.
Signal and terminal selection
The declaration confirms the DVP06AD-SH part number and input count. Verify the supply voltage, input ranges, resolution, conversion time and terminal layout against the wiring sheet for this exact model. Before replacing a module, match its full part number, terminal markings and existing cabinet diagram.
Check the output type when selecting a pressure transmitter, level sensor or position sensor. 0–10 V and 4–20 mA require different input circuits. When comparing voltage and current signals, check the sensor supply, current loop and supported input range together. For example, a change to the pressure sensor’s measuring range also calls for a change to the PLC scale in bar.
Route measurement cables away from motor and drive cables to reduce electromagnetic interference. Include analogue shield connections, grounding and the field supply in the panel layout. Determine the 24 V DC field supply and protective fuse from the sensor circuit requirements. The module’s DC classification describes the module supply.
PLC software, cable and measurement checks
Select the programming connection for the host PLC model and port. Compatible DVP CPUs use WPLSoft or ISPSoft. Configure the ISPSoft serial connection in COMMGR. For example, the DVP-SS2 CPU’s COM1 RS-232 port uses UC-PRG020-12A from PC USB or UC-MS020-01A from PC RS-232. These are examples of CPU-side programming cables. Verify the CPU compatibility, expansion position and register map for DVP06AD-SH in its own documentation.
On an existing machine, back up the ladder program and identify the PLC registers used for analogue readings. Apply low and high test signals within the confirmed range. Compare the raw values at both points with the engineering units on the HMI. For PLC PID control, express the feedback and setpoint in the same units. This also applies to PID speed control. For local display, consider separate analogue signal controllers.
Related models
DVP06AD-S provides six analogue inputs and DVP04AD-S2 provides four. For measurement and analogue control in one module, DVP06XA-S2 offers four inputs and two outputs. DVP04DA-S2 is a four-output option. Check the host CPU, signal range and PLC register layout in each model’s own manual.
Editor’s Note
Look for the full DVP06AD-SH code. For a used module, ask for clear photographs of the label, terminals and side connector.
Before removing a working module, record the channel numbers and sensor connections. Keep a copy of the PLC project.
If one channel drops out, start with its field supply and cable continuity. The sensor, wiring or module can produce the same symptom.
Record two stable test points. Comparing raw values with the screen units helps isolate wiring faults and scaling errors.
If the terminal and input range documentation is missing, start with the cabinet diagram. Apply a test signal only to a verified input and within its confirmed range.
PDF and references
See Delta DVP PLC files for series documentation. The appendix to the DVP Slim declaration identifies this part number. Use the model-specific wiring and operation document for supply terminals, signal ranges and the PLC register map.
Navigation · Delta automation · Delta PLC · DVP PLC series · Expansion modules · DVP06AD-SH model page