Delta UC-CMC100-01A
Delta UC-CMC100-01A — 10 m CANopen / DMCNET RJ45 Cable
Delta UC-CMC100-01A is a 10-metre industrial network cable with RJ45 connectors at both ends. It belongs to the Delta CANopen cables range. The AS accessory catalogue lists UC-CMC cables for suitable CANopen, DeviceNet and DMCNET connections. Verify the actual port’s protocol and pin assignment separately.
Application and port selection
The AS hardware manual identifies UC-CMC100-01A as a CANopen cable for the AS-FCOPM family. In a Delta AS PLC application, select the module, network devices and topology together. Use the correct devices and network settings in CANopen Builder as well.
An RJ45 socket alone does not identify an Ethernet interface. Select EtherCAT cables and UC-CMC cables according to their respective manufacturer connection definitions. On a DVP PLC or another device, do not make a trial connection simply because the plug fits.
Pin functions in the 2019 manufacturer drawing
| Pin | Colour | CANopen | DMCNET |
|---|---|---|---|
| 1 | Black | CAN+ | DMCNET_D1+ |
| 2 | Orange | CAN− | DMCNET_D1− |
| 3 | Brown | CAN_GND | DMCNET_D2+ |
| 4 | Gray | — | — |
| 5 | Blue | — | — |
| 6 | White | CAN_SHLD | DMCNET_D2− |
| 7 | Yellow | CAN_GND | DMCNET_GND |
| 8 | Green | — | DMCNET_GND |
The table follows the CANopen and DMCNET definitions on page 3-9 of the 2019-08-15 cable selection guide. “—” indicates no assigned signal in that drawing. Do not equate these colours with another Ethernet cable’s colour scheme. Use the connector view and pin numbering in the equipment manual.
10 m cable length and network topology
10 m is the physical length of this cable. Allowable total network length depends on the protocol, data rate, equipment, connectors and branch arrangement. A single cable’s length does not define the communication-distance limit of the whole system.
For DeviceNet, the ODVA guide limits the drop from a device to the trunk to 6 m maximum. Do not therefore assume a 10 m UC-CMC100-01A is suitable for a standard DeviceNet drop. Networks using UC-DN01Z-01A and UC-DN01Z-02A also require separate calculations for trunk, individual drop and cumulative drop lengths.
Distribution and termination
Review TAP-CN03 for RJ45 distribution arrangements, and TAP-CN01 or TAP-CN02 for their applicable terminal connections. Check accessory port types and network positions. Verify any required network power separately; do not apply power to unused or reserved pins.
Install termination according to the selected network’s manual. Relevant CANopen termination products include TAP-TR01; check DMCNET termination separately. Assess trunk ends and existing termination switches together instead of adding a resistor at every connection point.
UC-CMC length options
| Model | Length |
|---|---|
| UC-CMC003-01A | 0.3 m |
| UC-CMC005-01A | 0.5 m |
| UC-CMC010-01A | 1 m |
| UC-CMC015-01A | 1.5 m |
| UC-CMC020-01A | 2 m |
| UC-CMC030-01A | 3 m |
| UC-CMC050-01A | 5 m |
| UC-CMC100-01A | 10 m |
| UC-CMC200-01A | 20 m |
Measure the route with connector access and reasonable service clearance in mind. Avoid storing excess cable in a tight coil beside power equipment. Compare other products under Delta industrial network cables using the required protocol and port information.
Editor’s Note
Read the port designation at both ends first. Do not assume RJ45 means Ethernet or mix CANopen, DeviceNet and DMCNET functions. Record the complete module code and selected port.
Disconnect both ends and switch off power before measuring the cable. Check continuity, unintended shorts and shield connections against the applicable drawing. Do not treat every pin as a standard Ethernet connection without consulting the manufacturer diagram.
For a ten-metre cable fault, inspect both plugs and cable entries first. Correct broken latches, crushed insulation or movement-sensitive contacts. Comparison with a suitable, known-good shorter cable can help distinguish cable faults from equipment faults.
For intermittent communication, check data rate, node address, termination and routing in sequence. Change one setting at a time. Record the affected device and operating conditions when the fault occurs.
Measure the length of any branch leaving a distribution box. Keep DeviceNet drop limits separate from CANopen and DMCNET requirements. A 10 m label does not establish suitability for every topology.
For used equipment, request actual data exchange and a period of stable operation with suitable devices after continuity checks. Switch off power before changing plugs on an operating machine. Begin with safe status and data monitoring rather than motion commands.
PDF and related topics
Use the Delta PLC accessories PDF and software files page for cable selection and wiring documents. Further documentation is available under Delta PLC and HMI manuals and Delta user manuals.
Navigation: UC-CMC100-01A main page · Delta PLC accessories · Delta PLC models · Used Delta products
External references
Delta PLC/HMI Cable Selection Guide — 2019-08-15, 3-9 / 4-4 · Delta AS / AX-3 Catalogue — UC-CMC Cable Accessories · Delta AS Hardware and Operation Manual — AS-FCOPM Cables · ODVA — DeviceNet Cable System Planning and Installation