Delta UC-CMC005-01A
Delta UC-CMC005-01A 0.5-Metre CANopen Cable
Delta UC-CMC005-01A is a 0.5-metre (50 cm) CANopen communication cable with RJ45 connectors at both ends. It belongs to the Delta CANopen cables and Delta industrial network cables groups.
Compatible equipment and connection selection
The catalogue lists DVPCOPM-SL, DVP15MC11T, DVP15MC11T-06 and TAP-CN03 for the UC-CMC family. Verify the equipment model and designated CANopen port.
Terminal-block CANopen ports require an appropriate RJ45-to-terminal connection arrangement. Verify signal assignments as well as connector format. Matching RJ45 plugs alone do not establish electrical compatibility.
CANopen RJ45 pin assignments
Delta specifies 1 CAN+, 2 CAN−, 3 and 7 CAN_GND, and 6 CAN_SHLD. Pins 4, 5 and 8 are reserved.
Read pin numbers using the manufacturer's connector viewing direction. Match the latch and contact-face orientation; do not reverse assignments merely because opposing plugs appear numbered in opposite directions.
Short connections and bus termination
When choosing a 50 cm cable, measure the actual cable route. Include duct turns, connector entries and maintenance slack. Avoid an installation that pulls on the connectors.
Terminate the two physical ends of the CANopen bus. Delta specifies the TAP-TR01 terminator as 121 Ω. Set a distribution box's termination switch according to its position on the bus.
A short cable does not remove the complete network's termination and speed requirements. Assess total bus length, branches and node settings together. Route the cable separately from motor and drive power wiring.
Other length options
UC-CMC003-01A is 0.3 m; UC-CMC010-01A is 1 m, UC-CMC015-01A is 1.5 m, and UC-CMC020-01A is 2 m.
UC-CMC030-01A is 3 m, UC-CMC050-01A is 5 m, UC-CMC100-01A is 10 m, and UC-CMC200-01A is 20 m. Specify the complete cable code and equipment at both ends when ordering.
Editor's Note
Measure the route before choosing half a metre. Passing through ducts and turning at connector entries can increase the required length. Establish the route before selecting the cable.
Avoid pulling two sockets together with a short cable. A tight installation places vibration loads on plugs and sockets. Leave sensible slack for maintenance and removal.
Check both latches on a used cable. Inspect broken locks, discoloured contacts and crushed connector entries. If movement interrupts communication, investigate the contact first.
Unplug both ends before continuity measurements. Check the required conductors and shorts against the manufacturer's diagram. Do not apply high-voltage insulation testing while equipment remains connected.
Trace termination locations when diagnosing network faults. Identify the bus ends and inspect switches in intermediate distribution boxes. Avoid adding resistors indiscriminately at each connection.
Verify actual data exchange after replacement. Secure the machine and check node addresses, speed settings and command destinations. A clear maintenance record simplifies future fault finding.
PDF diagrams and software
Use our Delta PLC accessories PDF and software files page for documentation. Consult Section 3.5, Figure 1 and Section 4.1, CANopen of the Delta PLC/HMI Cable Selection Guide. For configuration, use an equipment-supported CANopen Builder version and the relevant device manual.
Related subjects
See Delta DVP PLC series for controllers, Delta PLC accessories and industrial network cables for connection products, and used Delta PLC models for equipment options.
Navigation: Used Delta products | Delta PLC models | PLC accessories | CANopen cables | PDF and software files
External references
Delta PLC/HMI Cable Selection Guide, manufacturer document | Delta DVP/TP catalogue, accessories