Delta UC-CMC015-01A
Delta UC-CMC015-01A
Delta UC-CMC015-01A is a 1.5-metre preassembled CANopen communication cable with RJ45 connectors at both ends. It provides the connection between compatible controller and drive ports. Select it by length, the actual network function of each port and the connection arrangement supported by the other device.
Applications in the manufacturer's guide
Delta's cable guide lists UC-CMC015-01A for the Delta DVP10MC11T in the Delta DVP-MC family using CANopen. The same guide also shows this cable with Delta AH20MC-5A using DMCNET. Verify the exact drive model and its network option against the drive documentation.
The cable carries signals; the connected device ports determine the network protocol. Listing the same cable for CANopen and DMCNET does not make it a converter between those networks. An RJ45 connector alone does not establish Ethernet or EtherCAT compatibility. Compare the separate cable group under Delta EtherCAT cables.
CANopen pin functions
The manufacturer's Figure 1 identifies pin 1: CAN+, pin 2: CAN−, pins 3 and 7: CAN_GND and pin 6: CAN_SHLD. Pins 4, 5 and 8 are marked “—” in its CANopen table. Read pin numbers together with the connector viewing direction; do not use unassigned contacts as supply connections.
The DMCNET section of the same drawing assigns 1/2: D1+/D1−, 3/6: D2+/D2− and 7/8: DMCNET_GND. Do not transfer CANopen signal names directly to a DMCNET port. Review connectors and distribution components separately under Delta network connectors.
Selecting length within the UC-CMC family
Shorter options are listed as UC-CMC003-01A at 0.3 m, UC-CMC005-01A at 0.5 m and UC-CMC010-01A at 1 m. UC-CMC015-01A provides 1.5 m. Measure the route through connector exits and cable ducts rather than simply between device front panels.
Longer options are UC-CMC020-01A at 2 m, UC-CMC030-01A at 3 m, UC-CMC050-01A at 5 m, UC-CMC100-01A at 10 m and UC-CMC200-01A at 20 m. These values describe individual cable lengths. Assess the complete CANopen network distance separately against its bit rate, trunk and branch arrangement.
Cable routing and network settings
When routing the 1.5-metre cable, allow for the turn behind each plug and maintenance access. Avoid stretching a short cable against its RJ45 latches. Prevent crushing at covers and duct edges, and route it away from motor and drive power wiring.
Check the physical ends of the CANopen bus and active termination against the device drawings. For distribution components such as Delta TAP-CN03, use the component's own port and termination documentation. Verify addresses, bit rate and device configuration independently of the cable.
Use the Delta CANopen Builder page in the context of supported controller and network-module configuration. UC-CMC015-01A does not require a separate cable driver; project and network settings are handled through the tools for the connected hardware.
PDF and connection documentation
Start document selection at Delta PLC accessories files. In the PLC/HMI Cable Selection Guide, printed page 3-7 / PDF page 148 provides the application table, and Figure 1, printed page 3-9 / PDF page 150 shows connectors and pin functions. Printed page 49 / PDF page 50 of the 2023 DVP/TP catalogue provides UC-CMC cable lengths.
Editor's Note
State the 1.5-metre length explicitly when ordering. Keep the old cable marking together with photographs of both device ports. Do not try to distinguish neighbouring one- and two-metre models by plug appearance alone.
Measure the actual route before removing the cable. Duct turns and space behind plugs change the required length. Choose a suitable length rather than leaving a short cable under tension.
Check continuity with both ends disconnected from equipment. Trace CAN+, CAN−, common and shield connections against the manufacturer pin drawing. Take care with numbering when viewing a plug from the front or rear.
If communication deteriorates when the drive starts, inspect cable routing too. Check proximity to power wiring, shield connections and plug seating. Record the operating condition that triggers the fault before replacing the cable.
Observe every station after replacement. Make a controlled comparison using a known-good cable with the correct code, and check error counters and node status. Confirm the result before closing the cabinet and completing the job.
Related topics
Browse parent groups under Delta CANopen cables and Delta PLC accessories, and device documentation under Delta PLC and HMI manuals.
External references: Delta PLC/HMI Cable Selection Guide — 2019, English · Delta DVP/TP manufacturer catalogue — 2023, English.