Delta UC-CMC200-01A

Delta UC-CMC200-01A 20-Metre CANopen Cable

Delta UC-CMC200-01A is a 20-metre CANopen connection cable with RJ45 connectors at both ends. It belongs to Delta CANopen cables and Delta PLC accessories. The manufacturer's cable guide also lists the UC-CMC family for documented DMCNET connections. Select the application according to the connected devices' ports and protocols.

Device connections and port checks

The DVP catalogue's related equipment includes DVP10MC11T, DVP15MC11T, DVPCP02-H2 and DVPCOPM-SL. DVPCOPM-SL uses a 5-pin removable CAN terminal, so the RJ45 cable does not plug directly into it. Select the required physical connection using Delta network connectors and the device wiring diagram.

The cable guide identifies the appropriate servo connection from AH20MC-5A as DMCNET. An RJ45 connector does not establish Ethernet operation or interchangeability with EtherCAT cables. Keep CANopen and DMCNET connections within their respective supported networks.

CANopen pin functions

In Figure 1 on page 3-9, the guide identifies pin 1 as CAN+, pin 2 as CAN-, pins 3 and 7 as CAN_GND and pin 6 as CAN_SHLD. Pins 4, 5 and 8 are unassigned in that table. Verify the device's port drawing and connector viewing orientation separately.

For DMCNET, pins 3 and 6 form the second data pair. Do not apply one protocol's signal names to the other connection. When repairing a cable, follow the manufacturer's diagram rather than relying solely on a familiar RJ45 colour sequence.

20-metre cable versus total network length

20 metres is the length of this cable. Permissible total CANopen distance depends on baud rate and device instructions. For example, the DVPCOPM-SL manual specifies 25 metres at 1 Mbit/s and 100 metres at 500 kbit/s. These are that module's network limits; assess all cable sections and the connection arrangement together.

The TAP-CN03 instruction sheet limits DeviceNet/CANopen drop cables to 6 metres. UC-CMC200-01A exceeds that limit and must not be selected as a drop cable in that arrangement. A catalogue accessory reference does not approve every cable length for every connection.

Arrange CANopen termination at the two physical network ends according to the equipment instructions. Check TAP-TR01 terminators together with existing device resistors. Adding a termination resistor at every node is incorrect.

Shorter cables and network configuration

Related lengths include UC-CMC100-01A at 10 metres, UC-CMC050-01A at 5 metres, UC-CMC030-01A at 3 metres, UC-CMC020-01A at 2 metres and UC-CMC010-01A at 1 metre. Select by route and permitted trunk/drop arrangement. See Delta industrial network cables for other cable types.

No software is installed in the cable. Configure node addresses, baud rate and data mapping in the network devices. Use Delta CANopen Builder according to controller or communication-module support.

Editor's Note

The 200 code identifies a 20-metre cable, not a 2-metre cable. Decide whether the connection is a link between devices or a drop from a distribution box before selecting length.

Record total network length and baud rate before installing the cable. At high speeds especially, measuring the new cable alone does not establish that the complete network is suitable.

Disconnect both ends before continuity testing. Compare CAN+, CAN-, signal ground and shield connections with the relevant port diagram. A broken connector latch can cause vibration-related interruptions.

For intermittent communication, test the same device pair with a short known-good cable first. Then inspect the long route and termination in sequence. Cable replacement will not correct node-address or baud-rate errors.

Keep the cable out of motor-power bundles and avoid tension at the connector entries. Confirm the cable's flexing and motion ratings before using it in a moving cable carrier.

PDF and wiring documentation

Use Delta PLC accessories files for the cable guide and accessory documents, and Delta PLC and HMI manuals for connected-device network instructions. Printed page 3-7 covers applications and page 3-9 shows the cable and pin definitions.

Related topics

Delta CANopen cables · Delta UC-CMC100-01A · Delta UC-CMC050-01A · Delta TAP-CN03 · Delta TAP-TR01

Return to Delta PLC accessories. Browse controllers in the Delta PLC category and available devices under second-hand Delta products.

External references: Delta PLC/HMI Cable Selection Guide (archived manufacturer document) · Delta Download Center