Delta IFD9502
Delta IFD9502 — DeviceNet / RS-232 and RS-485 Gateway
Delta IFD9502 is a communication gateway connecting serial equipment to a DeviceNet network. It operates as a DeviceNet slave for data exchange with suitable Delta equipment and supported Modbus devices. This unit in the Delta DVP interfaces range must be selected according to both the network protocol and the connected equipment’s communication requirements.
Main technical specifications
| Item | Value / description |
|---|---|
| Network protocol | DeviceNet, CAN-based |
| DeviceNet data rates | 125 / 250 / 500 kbit/s |
| Network supply | 11–25 V DC; nominal 24 V DC |
| Current | 28 mA typical; 125 mA impulse current at 24 V DC |
| Electrical isolation | 500 V DC |
| DeviceNet connector | Removable, 5.08 mm |
| Serial connections | PORT 1: RS-485; PORT 2: RS-232 or RS-485 |
The 125/250/500 kbit/s values apply to DeviceNet. The serial equipment’s baud rate and data format are set separately according to the selected equipment profile. Do not apply the same numerical speed to both connections automatically.
Network role and configuration
IFD9502 transfers data between a DeviceNet master/scanner and serial equipment using I/O polling and explicit messaging. A DVPDNET-SL configured as a master can act as the scanner in this arrangement. Configure the scan list and input/output mapping in DeviceNet Builder for the actual application. Detecting a node and reading the correct process data require separate verification.
Address, DIP switches and serial equipment profile
Two rotary switches set the DeviceNet node address within 00–63; 64–99 is invalid. DIP switches select the equipment type, serial interface and DeviceNet data rate. Address and DIP changes become effective after the unit is powered off and on again.
The application manual specifies serial address 1 and 38400 bit/s, RTU, 8N2 for its predefined VFD profile, and address 1 with 115200 bit/s, ASCII, 7E1 for its DVP PLC profile. These settings belong to the documented profiles and must not be applied automatically to other or custom equipment. Check the exact model’s communication support when selecting Delta DVP PLC series.
Serial ports and key signal pins
| Connection | Interface | Signal pins in the manual |
|---|---|---|
| PORT 1 — 6-pin socket | RS-485 | 2: GND · 3: DATA− · 4: DATA+ |
| PORT 2 — male DB9 | RS-232 | 2: RXD · 3: TXD · 5: GND |
| PORT 2 — male DB9 | RS-485 | 3: DATA− · 8: DATA+ |
Compare pin numbers with the connector view in the manual; viewing a plug from the wiring side can reverse its apparent orientation. A DB9 pin can have a different function in RS-232 and RS-485 modes. Verify signal mapping as well as mechanical fit when selecting DVP communication cables and Delta network connectors.
DeviceNet cable and termination
The DeviceNet connection uses V+ / V− for power, CAN_H / CAN_L for data and SHIELD for shielding. Among suitable industrial network cables, review UC-DN01Z-01A and UC-DN01Z-02A according to trunk and drop-line requirements.
Fit 121 Ω, 1%, minimum 1/4 W termination at both physical ends of the DeviceNet trunk. Do not add a resistor at every device or branch. Review TAP-CN01, TAP-CN02 and TAP-CN03 for distribution. TAP-TR01 has an RJ45 format and should not be treated as a direct plug-in part for IFD9502’s terminal connector.
Differences from IFD9503, IFD9506 and IFD9507
IFD9502 uses DeviceNet; IFD9503 uses CANopen; IFD9506 supports Modbus TCP and EtherNet/IP; and IFD9507 uses EtherNet/IP. Similar housings or serial ports do not make these protocols interchangeable. IFD6500 provides USB/RS-485 conversion and IFD6503 provides USB/CAN conversion for different connection requirements.
Diagnosis with LED indicators
NS indicates DeviceNet status, MS module status and SP serial equipment status. Flashing green NS means the device is online without an established master connection; solid red can indicate duplicate addressing or bus-off. Solid green SP indicates normal serial communication, flashing red indicates a CRC error or equipment error response, and solid red indicates a failed connection.
Editor’s Note
Identify the network first. DeviceNet, CANopen and EtherNet/IP are different protocols. Compare the module label, master device and existing project before ordering an IFD model that looks similar.
Measure supply voltage at the module terminals first. Correct voltage at the cabinet power supply does not prove that the same voltage reaches the end of a long cable. If the fault appears under load, check connections and voltage drop under those conditions.
Test the network and serial sides separately. First demonstrate that the serial device responds at the correct address and format, then verify DeviceNet mapping. Changing both sides together makes it harder to locate the fault.
Photograph the DIP and rotary settings before changing them. Record the settings and LED states after cycling power. When testing a working machine, arrange suitable stopping measures so that control commands cannot cause unexpected movement.
Check for loose connectors, corrosion and broken conductors before opening the module. Do not apply an insulation tester to CAN or serial communication lines. Comparison with a known-good cable, suitable supply and test device is more useful than replacing board components at random.
For used equipment, request more than a photograph of illuminated LEDs. Ask for a known-value read and a write to a safe test area through the master, recording the serial equipment and settings. Hardware response and correct application operation should be assessed separately.
Product lifecycle, PDF and related topics
Delta’s official product page lists IFD9502 as discontinued in June 2024. When selecting a spare for an existing installation, check the protocol, serial equipment profile and configuration files together.
Use the Delta PLC accessories PDF and software files page for manuals and software links. Further documentation is available under Delta PLC and HMI manuals.
Navigation: IFD9502 main page · Delta PLC accessories · Delta PLC models · Used Delta products
External references
Delta IFD9502 — Product Specifications · Delta IFD9502 — Application Manual · Delta IFD9502 — Instruction Sheet · Delta IFD Series — FAQ · ODVA — DeviceNet Cable System Planning and Installation · Delta IFD9502 — Product Lifecycle