Delta UB-10-IO16C / DVPAETB-IO16C
Delta UB-10-IO16C / DVPAETB-IO16C — External Terminal for AH04HC and AH20MC
Delta UB-10-IO16C / DVPAETB-IO16C is a 36-pin HDC external terminal assembly that brings the local I/O connections of AH04HC-5A and AH20MC-5A modules to field terminals. It belongs to the Delta AH external terminals range and provides accessible panel terminals for connector-based modules in Delta AH PLC series applications.
Compatible modules and 36-pin cable
The catalogue identifies AH04HC-5A as a 4-channel high-speed counter and AH20MC-5A as a DMCNET motion-control module. For both, the cable guide shows CN1 external I/O → UC-ET010-13B → UB-10-IO16C.
UC-ET010-13B is a 1 m cable with female MDR36 connectors at both ends. Hardware documents also show it alongside DVPACAB7D10. Review cable options under Delta AH I/O cables.
Technical and mechanical information
| Item | UB-10-IO16C / DVPAETB-IO16C |
|---|---|
| Applicable modules | AH04HC-5A / AH20MC-5A |
| Connection | CN1 external I/O, HDC / MDR36 |
| Cable | UC-ET010-13B / DVPACAB7D10, 1 m |
| Mounting | DIN-rail base |
| Width × depth × height | 125 × 87 × 50.8 mm |
Input pairs, outputs and common terminals
| Marking group | Connection in the manual |
|---|---|
| X0.0± … X0.3± | 4 differential input pairs |
| X0.8± … X0.15± | 8 differential input pairs |
| Y0.8 / C0 · Y0.9 / C1 · Y0.10 / C2 · Y0.11 / C3 | 4 outputs and their respective common terminals |
| 24V / 24G | Supply connections |
| FE | Functional earth |
| N/C | Unassigned terminals |
The table groups the terminal arrangements on pages 3-97 and 3-98 of the manufacturer hardware manual. Input-pair count does not equal the number of independent counter channels. The selected module and its settings determine counting, capture, reset or other signal functions.
Keep the 24V and 24G supply terminals distinct from differential “+” and “−” inputs. Check the module’s accepted electrical levels before connecting an encoder or another signal source. AH20MC-5A’s DMCNET network connection is separate from this local I/O terminal.
Selection differences from IO22C, IO24C and IO34C
| Module | Cable | External terminal |
|---|---|---|
| AH04HC-5A / AH20MC-5A | UC-ET010-13B | UB-10-IO16C / DVPAETB-IO16C |
| AH10EMC-5A | UC-ET010-13B | UB-10-IO22C / DVPAETB-IO22C |
| AH10PM-5A | UC-ET010-15B | UB-10-IO24C / DVPAETB-IO24C |
| AH15PM-5A | UC-ET010-15B | UB-10-IO34C / DVPAETB-IO34C |
Although AH10EMC-5A uses the same UC-ET010-13B cable, the guide pairs it with IO22C. The IO24C / IO34C units for AH10PM-5A and AH15PM-5A instead use the 50-pin cable family shown as DVPACAB7E10 / UC-ET010-15B. Do not substitute a terminal solely because the connector fits.
Editor’s Note
Read the full module code and terminal label together. Do not identify IO16C, IO22C, IO24C or IO34C by appearance alone. In particular, the shared cable code for IO16C and IO22C does not establish identical terminal arrangements.
On a used assembly, inspect HDC contacts, connector retainers, screw terminals and the rail clip. Corrosion, cracked housing or loose terminals can cause intermittent faults. Check cable entries for crushing as well.
Switch off power and disconnect the module cable and field wiring before continuity checks. Follow the connector viewing direction in the manual when checking contact-to-terminal paths and adjacent contacts for shorts. Do not bridge N/C terminals.
If pulses are missed, inspect signal-source output type, signal level, differential pairs and routing alongside the terminals. With a suitable test signal, compare the applied pulses with the count reported by the module.
When checking Y0.8–Y0.11 outputs, trace the corresponding C0–C3 common terminals as well. Verify the module’s output type and current limit before connecting a load. The terminal assembly does not increase output-current capability.
Begin operating tests under conditions that prevent unexpected machine movement. Verify the inputs and required outputs individually. A single working channel does not establish that an entire repaired assembly is sound.
PDF and related topics
Use the Delta PLC accessories PDF and software files page for wiring and installation documents. Further documentation is available under Delta PLC and HMI manuals and Delta user manuals.
Review system components under Delta AH500 and AH Motion backplanes. Confirm controller and rack selection against their own compatibility tables.
Navigation: UB-10-IO16C / DVPAETB-IO16C main page · Delta PLC accessories · Delta PLC models · Used Delta products
External references
Delta AH Series Catalogue — Accessory Selection, 34–35 · Delta AH500 Hardware Manual — 3-92 / 3-97–98 · Delta PLC/HMI Cable Selection Guide — 2-25–26, Figure 13