Delta DVP08SP11R
Delta DVP08SP11R 4-Input 4-Relay Output Module
The Delta DVP08SP11R is a mixed digital expansion module that adds four 24 V DC inputs and four relay outputs to a compatible DVP Slim PLC. The inputs read sensors and contacts. The relay outputs can switch panel indicators, interposing relays or suitable coil circuits.
See Delta DVP PLC files for wiring diagrams and expansion I/O addressing.
Inputs and relay contact ratings
Inputs. X0–X3 are rated at 24 V DC and 5 mA per channel. Input response is approximately 10 ms. For three-wire DC sensors, connect S/S to 0 V for PNP and S/S to +24 V for NPN. All four inputs share the S/S common. The PLC expansion bus powers the module electronics.
Outputs. Each relay has a normally open contact pair. The terminal pairs are C0–Y0, C1–Y1, C2–Y2 and C3–Y3. Feed the load circuit supply to the relevant C terminal. Delta’s 2026 model diagram specifies 10–240 V AC or 5–30 V DC. The resistive-load rating is 1.5 A per output and the manual lists 5 A per common.
Sensor and load examples
On a fixture, an inductive sensor can detect the part and a limit switch can report the end of travel. When replacing a sensor, check the PNP or NPN output and its NO or NC operation separately. Choose sensors for the shared S/S terminal according to the sink or source wiring.
If a relay contact switches a solenoid or contactor coil, check the coil voltage, pickup current and switching frequency. Delta shows a suitably rated flyback diode for a DC coil and an appropriate RC suppressor for an AC coil. In a motor circuit, the contactor switches the main power. The PLC relay drives the coil of a suitably selected contactor. See the difference between a relay and a contactor for load selection.
CPU compatibility, X/Y addressing and programming
Fit the module to the right-side expansion bus of a compatible CPU. Check the host’s expansion capacity in DVP-SS2, DVP-SA2, DVP-SX2, DVP-SV2 and DVP-SE projects. Under the addressing scheme in Delta’s instruction sheet, when fitted as the first digital expansion, the physical channels are X20–X23 and Y20–Y23. The module is allocated eight X and eight Y addresses in that scheme. X24–X27 and Y24–Y27 are reserved gaps.
Monitor the inputs and outputs through the CPU in WPLSoft or ISPSoft. For the DVP14SS211R, use UC-PRG020-12A on COM1 RS-232. For the DVP12SE11R, use an RJ45 network cable at the CPU’s Ethernet port. See DVP programming cables for other connections.
Editor’s Note
Check the suffix on a used module. Confirm 08SP11R on the label. Inspect the terminals, side-bus connector and retaining clips.
Test each input. Verify S/S wiring and apply a 24 V DC test signal. The input indicator and the PLC X bit should identify the same channel.
Test all four contacts under load. On the bench, use a suitable low-voltage test load to verify that each C–Y pair opens and closes.
Inspect the coil circuit too. If a contact repeatedly fails, check coil pickup current, suppression and switching frequency.
Mark the address gaps. If module order changes, compare the first and last physical channels with the original program. Mark the reserved X/Y addresses on the terminal schedule.