Delta DVP08SP11T
Delta DVP08SP11T – Digital Expansion Module with 4 Inputs and 4 NPN Outputs
The Delta DVP08SP11T adds four 24 V DC digital inputs and four NPN transistor outputs to a compatible Delta DVP Slim PLC. It connects to the CPU’s right-side expansion bus. A typical application is reading inductive sensors, photoelectric sensors or limit switches at a machine station and switching compatible DC control loads.
Input wiring and S/S common
X0–X3 are 24 V DC inputs. Delta’s model diagram gives approximately 5 mA per input, and the specification table gives a response time of approximately 10 ms. All four inputs share S/S. Connect S/S to 0 V for PNP sensors or to +24 V for NPN sensors. Connect the sensor signal wire to the appropriate X input.
Trace the signal’s current path when checking sink/source wiring. An active PNP sensor supplies current to X from +24 V. An active NPN sensor pulls X toward 0 V. The S/S connection completes the current path through the input optocoupler. When replacing a sensor, verify its output type and the S/S connection as well as the wire colors.
NPN outputs and C0–C3 wiring
Y0–Y3 switch 5–30 V DC load circuits. The terminal pairs are C0/Y0, C1/Y1, C2/Y2 and C3/Y3. For Y0, connect the 0 V side of the external 24 V DC supply to C0 and connect the load between +24 V and Y0. When Y0 turns on, current flows from +24 V through the load and Y0 to C0/0 V. Use each remaining channel’s corresponding C and Y terminals in the same way.
Allowable current per channel depends on the temperature inside the panel. Delta specifies 0.30 A at 40 °C, 0.20 A at 45 °C, 0.15 A at 50 °C and 0.10 A at 55 °C. A DC load drawing 180 mA exceeds the channel rating at 50 °C. When using an interposing relay or another DC coil, check its current and select a suitable flyback diode. Routing signal wiring separately from motor cables helps reduce electromagnetic interference.
PLC input and output addresses
The X and Y numbers on the terminal block are local labels. The CPU and expansion order determine the program addresses for the PLC I/O modules. In a classic Slim configuration where the first expansion starts at X20 and Y20, this module uses X20–X23 and Y20–Y23. Each four-point side reserves an eight-address block, so the upper four addresses in each block have no physical terminal.
Programming software and cable
Download the PLC program to the host CPU using a compatible release of WPLSoft or ISPSoft. Configure the ISPSoft connection through COMMGR. For the DVP-SS2 COM1 RS-232 port, use the UC-PRG020-12A from a PC USB port or the UC-MS020-01A from a PC serial port. The UC-PRG015-01A can be used with the DVP-SX2 mini-USB port.
Editor’s Note
When buying a used module, check the suffix on the label. T identifies NPN outputs, TS identifies PNP outputs and R identifies relay outputs.
Before removal, photograph the S/S connection and the C–Y terminal order. Compare the wire labels with the actual X and Y addresses in the program.
If all four inputs fail to respond, check the sensor supply and S/S polarity first with a multimeter.
If an output LED is on and its load remains off, check the associated C terminal’s 0 V return and the fuse in the load’s +24 V feed. On the bench, test each channel with a suitable 24 V DC load.
If the fault develops as the panel warms up, measure the coil or load current and compare it with the channel rating at the temperature around the module.
Related models and products
The DVP08SP11TS has four inputs and four PNP outputs. The DVP08SP11R has four inputs and four relay outputs. The DVP16SP11T provides eight inputs and eight NPN outputs. The DVP08SN11T adds eight NPN outputs. For standalone control projects, see the Derell B Series PLCs.
Manual and wiring diagram
The model’s terminal diagram appears in the 2026 edition of the DVP Series Module Manual, section 7.4.13, page 7-17. See Delta DVP PLC files for series documentation.
DVP08SP11T · DVP Slim digital modules · Used Delta PLC models · Delta Automation