Delta DVP08SP11TS

Delta DVP08SP11TS – 4 Digital Inputs and 4 PNP Outputs

Delta DVP08SP11TS is a mixed expansion module adding four 24 V DC digital inputs and four PNP transistor outputs to a compatible DVP Slim PLC system. It belongs to the DVP Slim digital module family and requires a host CPU. It provides extra sensor and control points while retaining the existing main controller and application.

The TS suffix identifies sourcing/PNP outputs. Its load wiring differs from the NPN DVP08SP11T. Understanding NPN and PNP matters for both sensor connections and output loads. This model handles digital on/off states rather than analog measurement values.

Electrical specifications and supply

Inputs: X0–X3, 24 V DC, approximately 5 mA per input and approximately 10 ms response. The ON threshold is above 16.5 V and the OFF threshold below 8 V. The S/S common connection determines the sinking or sourcing input arrangement.

Outputs: Y0–Y3, PNP/sourcing transistors; 5–30 V DC load circuit, maximum 0.3 A per output and 2 A per common group. The manufacturer specifies 0.3 A per PNP output at 55 °C. Four channels at 0.3 A each total 1.2 A; observe both channel and common-group limits.

UP/ZP supply: External 24 V DC, −15% / +20%, corresponding to 20.4–28.8 V. Include the connected loads when sizing the 24 V power supply. Body dimensions: 25.2 × 90 × 60 mm; 35 mm DIN rail mounting. Operating temperature is 0–55 °C.

S/S, UP and ZP wiring

Connect UP to +24 V and ZP to 0 V. Connect each load between its Y output and 0 V. When enabled, the output transistor supplies positive voltage from UP to the load. Recheck the circuit when replacing an NPN card; a PNP output is not a voltage-free relay contact.

Assess the input common separately: S/S normally connects to +24 V for an NPN sensor and to 0 V for a PNP sensor; the sensor output connects to the relevant X input. Verify the sensor supply and common reference. PNP outputs do not restrict the module to PNP input sensors.

Before driving a DC relay or contactor coil, check operating and pickup current. Fit a suitable suppression diode in accordance with the manufacturer's circuit. Consider the fuse, wire size and grounding arrangement as part of the load circuit. An illuminated output LED does not establish that the channel works under load.

Addressing, software and programming cable

No separate application is downloaded to this module. Develop the PLC program using WPLSoft or ISPSoft, as supported by the host CPU. ISPSoft communication uses COMMGR. The Ladder application accesses the module as ordinary X inputs and Y outputs.

In the classic DVP Slim addressing arrangement, the first digital extension starts at X20/Y20. At that position, this module has physical inputs X20–X23 and outputs Y20–Y23. Each four-point side reserves an eight-address block; X24–X27 and Y24–Y27 have no corresponding terminals. Check the actual project's I/O table because preceding modules and the CPU generation affect allocation.

The programming cable connects to the host CPU. For a suitable CPU with an 8-pin mini-DIN RS-232 port, cable options include UC-MS020-01A (2 m), UC-MS030-01A (3 m) and UC-PRG020-12A (2 m) for a PC USB connection. Verify the exact CPU and port against the cable selection guide. DVP08SP11TS has no programming port or independent Modbus station address.

Before installation, verify the exact CPU's right-side expansion support, module limit and supply capacity. Similar connector appearance alone does not establish compatibility.

Practical applications

On a conveyor or packaging station, an inductive sensor can detect a metal part, a photoelectric sensor can detect product passage and a limit switch can report mechanical position. The program combines these states to sequence a valve or interposing relay. In automation design, output type, pulse duration and input response matter alongside sensing distance. Assess dedicated high-speed inputs before using this standard extension for short pulses or fast encoder signals.

For mechanisms with forward/reverse movement, complement software interlocking with suitable electrical interlocking. Design the emergency stop and safety relay circuit according to the machine's safety requirements; this standard I/O module is not a safety controller. When replacing a timer relay function with a PLC timer, define power-loss behavior and restart conditions as well.

Related modules

DVP08SP11R provides four inputs and four relay outputs; DVP08SP11T provides four inputs and four NPN outputs. For more mixed I/O, DVP16SP11TS offers eight inputs and eight PNP outputs. For output-only expansion, DVP08SN11TS offers eight PNP outputs. Compare these by application requirements and recheck CPU support, terminal layout and load ratings before replacement.

Editor's Note

Read the final S on the label before wiring the card. DVP08SP11T and DVP08SP11TS look similar, but the load connection differs.

When inspecting a used module, activate all four inputs individually and observe both the input LEDs and CPU X bits. One working channel does not verify the other three.

Test every output separately with a small DC load of known current. Measure voltage between Y and ZP with the load connected; an unloaded reading alone is insufficient.

If POWER is on but a load does not operate, check UP/ZP supply, the return path and addressing. Perform short-circuit or resistance checks with power isolated, and disconnect field wiring to assess the card and load separately.

Replacing a failed output card is insufficient if its coil load caused the damage. Check coil current, suppression, loose terminals and supply ripple, then repeat the test under load after repair.

For a used-unit sale, state quantity, label photographs, working/faulty condition and channel test results. Sales require an invoice; no returns; workshop testing is available. Sellers can send details to otomasyonavm@gmail.com.

PDF documents and related topics

For wiring, addressing and cable selection, visit our Delta DVP PLC files page first. The shared DVP-Slim sheet covers several models; use the four-input/four-sourcing-output entry and PNP wiring for DVP08SP11TS.

Related topics and navigation: Delta and used models | Delta PLC | DVP series | Expansion modules | Slim digital modules | DVP08SP11TS model page

External references

Delta DVP-Slim manufacturer instruction sheet – 21 February 2024, multilingual
Delta DVP Series Module Manual – 6 January 2026, section 7.4.16
Delta PLC/HMI Cable Selection Guide