Delta TP04P-32TP1R
Delta TP04P-32TP1R Keypad Operator Panel with Built-in PLC
Delta TP04P-32TP1R combines a 4.1-inch, 192×64-pixel monochrome STN-LCD and PLC control in a keypad-operated unit. This model in the Delta TP04P family provides 16 digital inputs and 16 relay outputs. The number 32 identifies its total physical digital I/O count. Within Delta TP panels and remote I/O, it is a PLC-integrated panel that executes its own control program.
The physical front-panel keys support page navigation, value entry and commands assigned in the project. Small machines can combine sequential control with displays for operating steps, counts, timers and alarms. Actual behaviour depends on the loaded PLC program and screen project.
16 digital inputs and addressing
Input addresses are X0–X7 and X10–X17; outputs are Y0–Y7 and Y10–Y17. X/Y addressing uses octal notation, so X10 follows X7 without skipping a physical input. Inputs are in the 24 V DC class. Check PNP/NPN sensor wiring together with the relevant S/S0 and S/S1 commons and the manufacturer's wiring diagram.
Relay outputs and loads
32TP1R is the relay-output version. Y0–Y7 share C0, while Y10–Y17 share C1. The manufacturer's resistive-load limits are 1.5 A per output and 5 A per common; calculate the combined current within each group. Coils and contactors need suitable suppression and, where necessary, interposing relays. Mechanical relay outputs should not be selected for high-speed pulse-train generation.
Programming and communication
The screen project can be created in Delta TPEditor and PLC ladder logic in Delta WPLSoft. If using Delta ISPSoft, verify the software version and target-device support. Keep screen and PLC backups separately and match both to the machine's existing revision during replacement.
The unit provides USB Type-B for program transfer and RS-485 COM2 and COM3 for field communication. Serial connections use removable terminals. When selecting Delta PLC cables or HMI programming and HMC cables, check port functions, pin assignments, station address, transmission rate and protocol together.
Supply, installation and model differences
The nominal supply is 24 V DC. Overall dimensions are 175.8×108.6×59.2 mm, with a nominal 163×96 mm panel cutout. Use the installation drawing for tolerances and mounting requirements. Leave sufficient clearance for rear terminals and cables when opening the cabinet door.
TP04P-16TP1R provides 8 inputs/8 relay outputs. TP04P-22XA1R adds voltage/current analogue channels, while TP04P-21EX1R provides current and Pt100 channels. TP04P-32TP1R has no built-in analogue or Pt100 channels. When comparing TP70P-32TP1R, examine display, project and terminal arrangements separately; matching I/O counts do not establish interchangeability.
Editor's Note
Start by saving the screen project and PLC program. Record parameters, recipes and communication settings as well; a program file alone may not preserve every setting needed to restore the machine.
Test every front-panel key. Investigate keys that need excessive pressure, generate double commands or fail to respond. Check display contrast and backlighting; examine the supply and contrast setting before deciding that a faint display needs a replacement LCD.
Test both input groups separately. Eight working inputs do not prove the other eight are healthy. Check the second group's common, terminals and program addresses as well.
Do not judge outputs by relay clicks. Measure the contacts with power removed, then test with a suitable small load. A C0 or C1 connection fault can make a whole output group appear defective; check the common before condemning all sixteen relays.
During repair, inspect terminal joints, supply circuitry and relay contacts. If a load remains on despite an off command, check for welded contacts and field-wiring faults. Bench-test the controller safely away from the machine. A powered display alone is insufficient evidence that the controller works.
Site resources and PDF pages
Related document sections are Delta TP panel files, Delta HMI Files and Delta PLC and HMI manuals. Manufacturer catalogue and programming-manual links are provided under External references below.
Related topics
For colour panels, see Delta TP70P; for analogue and temperature configurations, compare TP70P-22XA1R and TP70P-21EX1R. A conversion involving Delta DOP-100 also requires a decision about where PLC logic will run. For a separate PLC architecture, consult Delta DVP PLC series.
Connection and maintenance topics: Delta HMI modules and accessories · HMI mounting and power connections · HMI communication peripheral units.
Navigation
Delta PLC main group · Second-hand Delta products
External references
Delta DVP and TP series catalogue — English; display, dimensions and model-selection tables
Delta DVP and TP programming manual — English; includes TP04P-32TP1R
Delta TP04P installation and wiring sheet — multilingual, including English; archived copy