Delta TP70P-21EX1R
Delta TP70P-21EX1R Touch Panel with Built-in PLC
Delta TP70P-21EX1R combines a 7-inch, 800×480-pixel colour touchscreen and PLC control in one unit. This model in the Delta TP70P family provides 8 digital inputs, 8 relay outputs, 2 analogue current inputs, 1 analogue current output and 2 Pt100 temperature inputs. Within Delta TP panels and remote I/O, it is a PLC-integrated panel that executes its own program and has physical I/O.
It can serve small machines requiring temperature monitoring alongside current signals from pressure, level or flow transmitters. For example, two Pt100 sensors can monitor temperature while the analogue output supplies a speed reference to a compatible drive. The actual control function depends on the PLC program, selected signal ranges and connected equipment.
Digital inputs and relay outputs
Digital inputs use X0–X7 and relay outputs use Y0–Y7. Inputs are in the 24 V DC class; check the sensor's PNP/NPN arrangement together with the S/S common-terminal wiring. The manufacturer's resistive-load rating is 1.5 A per output and 5 A per common. Inductive loads such as coils and contactors require suitable suppression and, where necessary, an interposing relay.
Current and Pt100 channels
The two current inputs and single current output support 0–20 mA or 4–20 mA, according to channel configuration. Their digital scale is 0–4000. The two temperature channels accept 2-wire or 3-wire Pt100 sensors, with a −20…+160 °C range and 0.1 °C temperature increments. A thermocouple or current-transmitter output must not be connected to a Pt100 input.
In the PLC, D1110/D1111 hold current-input values, D1112/D1113 hold Pt100 temperatures and D1116 controls the current output. D1115 selects current-channel operating modes. Temperature data uses 0.1 °C units: 250 represents 25.0 °C. Check the screen's units and scaling against the PLC's raw values.
Programming, communication and installation
The screen project is prepared in Delta TPEditor, while PLC logic is developed using Delta WPLSoft or Delta ISPSoft with the appropriate target selected. Back up the screen project and PLC program separately. USB supports program transfer and monitoring. RS-485 COM2 serves PLC communication and COM3 serves panel communication. When choosing Delta PLC cables or HMI programming and HMC cables, check pin assignments, port functions and communication settings alongside connector type.
The supply is 24 V DC. The model-specific installation sheet gives overall dimensions of 205.6×142.6×49 mm and a nominal panel cutout of approximately 191×128 mm. Use the installation drawing for exact cutout tolerances and panel thickness. Label terminals, commons and field cables before replacing the unit.
Differences from other TP70P models
TP70P-16TP1R provides 8 inputs/8 relay outputs, while TP70P-32TP1R provides 16 inputs/16 relay outputs. TP70P-22XA1R has 4 analogue inputs and 2 analogue outputs for voltage/current signals. The 21EX1R combines current channels with two dedicated Pt100 inputs. When considering another version, including TP70P-RM0, compare physical I/O, terminal functions and the program together.
Editor's Note
Take a little time with this unit before accepting it just because the display lights up. Save both projects first, test the touchscreen across its full area, and check every input and relay output on a safe bench setup.
A clicking relay does not prove that its contacts are healthy. Check the contacts with power removed, then test with a suitable small load. Investigate discoloured terminals, loose connections and unstable operation under load before declaring the unit serviceable.
Disconnect the Pt100 sensor from the controller before measuring its resistance. A Pt100 simulator or suitable precision resistor makes comparison easier; according to the sensor standard, 100 Ω corresponds to approximately 0 °C. Compare both channels under identical conditions and account for lead resistance and wiring arrangement.
Test current inputs at 4, 12 and 20 mA using a calibrator. If readings are unexpected, check the 0–20/4–20 mA selection and screen scaling before blaming the analogue circuitry. Measure the current output separately with a compatible test load.
During repair, examine the supply circuit, connector joints, relay contacts and analogue-input area separately. Do not apply 24 V to analogue terminals as a test. For a second-hand purchase, request the full model label, terminal photographs and recorded test results. A working display does not establish that the complete controller has been tested.
Site resources and PDF pages
Related document sections are Delta TP panel files, Delta HMI Files and Delta PLC and HMI manuals. The manufacturer's model-specific installation sheet and TP70P Quick Start are linked under External references below.
Related topics
Compare the smaller PLC-integrated panel family under Delta TP04P, including TP04P-21EX1R and TP04P-22XA1R. For a separate PLC architecture, consult Delta DVP PLC series. These links are comparison resources and do not establish direct interchangeability.
For field connections and installation, see Delta HMI modules and accessories, HMI mounting and power connections and HMI communication peripheral units.
Navigation
Delta PLC main group · Second-hand Delta products
External references
Delta TP70P-21EX1R installation and wiring sheet — multilingual PDF including English and Turkish
Delta TP70P Quick Start — English; particularly sections 1.5, 1.8 and 3.9