Delta HMI Programming and HMC Cables
Delta HMI programming and HMC cables cover PC-to-panel programming, panel-to-PLC communication and handheld HMC connection assemblies. UC-PRG, UC-MS, HMC-CA and NC-CAB-DMC references serve different purposes. Selection starts with the full device models and the function of each port; connector shape alone does not establish compatibility.
In Delta HMC07 and Delta HMC08 systems, a handheld connection assembly is different from the USB cable used to transfer a project from a PC. Depending on the model, an HMC assembly may carry power, communications and safety contacts. DMCNET cables for HMC remote I/O modules form another group.
USB, serial and Ethernet programming cables
UC-PRG015-02A — 1.5 m; UC-PRG030-02A — 3 m: The cable guide identifies these as USB Type-A ↔ USB Type-B data cables. The panel must provide the corresponding programming port. A USB Host socket intended for a flash drive or printer must be distinguished from the USB Client/Device connection used with a PC. Check the exact port arrangement on DOP-B and DOP-100 models. Reference: 2019 cable guide, PDF p.97, Figure 19.
UC-PRG030-10A — 3 m: A female DB9 ↔ female DB9 serial cable. The source drawing shows crossed Tx/Rx connections; an ordinary straight-through DB9 extension is not an equivalent. Read the additional null-modem adapter arrangement together with its connection scenario. An RS-232 cable must not be connected to an RS-422 or RS-485 port merely because the connector fits. Reference: PDF pp.94–95, Figure 12.
UC-PRG020-12A — 2 m: A programming cable with USB-to-serial conversion. Describing it as a passive DB9-to-Mini-DIN lead is incorrect. Figures 3A/3B show USB together with 8-pin male Mini-DIN and female DB9 connection options, plus a male-to-male DB9 adapter accessory. Verify the selected end, adapter and target device pinout together. Reference: PDF p.90.
Appendix B of the 2019 guide describes the CP210x VCP driver for UC-PRG020-12A. After correct installation, check the COM number under Silicon Labs CP210x USB to UART Bridge (COMx) in Windows Device Manager and select that COM port in the software. Confirm the actual cable hardware identity and operating system before using the Delta download centre or official Silicon Labs CP210x driver page. Operating system examples in the old guide do not establish support for every current system. Reference: PDF pp.174–175.
UC-PRG030-20A — 3 m: Shown for RJ45 ↔ RJ45 Ethernet connections. The panel must support Ethernet and the selected project transfer method. Check IP addressing and subnet settings as well. An RJ45 socket is not necessarily Ethernet; this cable is not a replacement for DMCNET or a serial connection with a special pinout. Reference: PDF p.92, Figure 7. Review HMI Ethernet expansion modules and communication peripheral units separately when an additional interface is needed.
Panel-to-PLC serial communication cables
UC-MS020-06A — 2 m; UC-MS030-06A — 3 m: Male DB9 ↔ 8-pin male Mini-DIN cables. The guide provides an RS-232 wiring diagram for panel-to-PLC communication. These cables do not include the USB conversion function of UC-PRG020-12A, and their DB9 connector gender differs. Match port numbers, wiring drawings and electrical standards at both devices. Protocol, station address, baud rate, data bits and parity must also agree in the project settings. Reference: PDF p.91, Figure 4.
A serial connection on a legacy DOP-A, DOP-AE or DOP-AS panel does not establish universal cable compatibility with TP text panels. For TP04P and TP70P, also identify whether the selected port is used for programming or PLC communications. Select TPEditor or the appropriate DOPSoft/Screen Editor generation for the panel; these applications are not general substitutes for each other.
Handheld HMC cables: C0 and A0 references
HMC-CA3205C0 — 5 m; HMC-CA3210C0 — 10 m: The 2019 and 2021 HMC accessory tables list these as 32-pin connection cables for handheld HMC07-N5xx units. HMC-CA1205C0 — 5 m is listed as 12-pin in the same tables. These are not general-purpose USB programming cables.
HMC-CA1210C0 — 10 m: The catalogue editions disagree about the pin count. The examined English 2019/2021 tables state 32-pin, while Delta’s Chinese HMC catalogue states 12-pin. Do not infer confirmed compatibility from the “12” portion of the code or by copying the preceding row. Before purchase or replacement, verify the pin count against the device label, cable label and wiring drawing for that exact model.
Legacy A0 connection types: The HMC07-N500H52 instruction sheet shows HMC-CA3203A0 / HMC-CA3205A0 / HMC-CA3210A0 for 32-pin Type A; HMC-CA1203A0 / HMC-CA1205A0 / HMC-CA1210A0 for 12-pin Type A; and HMC-CA1603A0 / HMC-CA1605A0 / HMC-CA1610A0 for 16-pin Type A. In each group the lengths are 3 m / 5 m / 10 m, respectively. These A0 records do not establish interchangeability with C0 cables; device suffixes such as H52 must be retained.
Where the handheld assembly carries emergency-stop and three-position enabling-switch circuits, verify those connections separately using the device instructions. Successful communication does not confirm correct safety-contact wiring. Check mounting and power connections and HMI power supplies against the functions carried by the assembly.
DMCNET and remote I/O cables
NC-CAB-DMC003 — 0.3 m; NC-CAB-DMC015 — 1.5 m; NC-CAB-DMC050 — 5 m; NC-CAB-DMC100 — 10 m: HMC catalogues list these for DMCNET / Remote I/O connections. Select them for the supported HMC, servo or remote I/O port. They do not perform the same function as a standard Ethernet programming cable. A remote I/O model using RS-422 must not be assumed to use DMCNET cables. The connection path for local digital I/O expansion must also be distinguished from the remote I/O network. Reference: 2019 HMC catalogue PDF p.13; 2021 edition PDF p.15.
Editor’s note
Start with the full labels of both devices. “Delta cable” is not a specification. Record the panel and PLC models, port names, both cable ends and the complete cable reference together.
If a USB connection is not detected, check with a known data cable and a working PC USB port. For UC-PRG020-12A, inspect the COM entry and driver; for a USB A–B cable, inspect the panel’s own USB connection. They require different checks.
Before replacing a serial cable, compare RS-232/422/485 selection, port number, station address and parity. A wrong port or protocol can make a serviceable cable appear faulty.
For continuity checks on a passive cable, isolate power, disconnect both ends and use the manufacturer’s pin diagram. A USB converter contains electronics and must not be assessed as a simple wire harness. Avoid probing arbitrary pins while connected to powered equipment.
Inspect the frequent bending points of an HMC cable, connector locks, shield connections and signs of crushing. Communication checks and emergency-stop/enabling-circuit checks are separate tasks. Follow the machine’s defined verification procedure after replacement; do not bridge safety contacts for testing.
Keep the working cable’s full reference, length, adapters and communication settings in the machine records. Document A0/C0 distinctions and the HMC-CA1210C0 catalogue discrepancy so the next replacement is not chosen by connector shape alone.
Related topics and manuals
Panel generations: DOP-H07 · DOP-W · DOP-107H. Accessories: printer expansion modules · starter kits · HMI modules and accessories. These links support device and port checks; they are not a list of confirmed cable compatibility.