Delta TP04P-22XA1R — Keypad PLC Panel with Analog I/O

Delta TP04P-22XA1R combines a 4.1-inch monochrome STN LCD, physical keypad and built-in PLC within the Delta TP04P family. Display resolution is 192 × 64 dots and the nominal supply is 24 V DC. In the TP panels and remote I/O group, it suits applications requiring operator data entry and machine control involving analog signals.

It provides 8 digital inputs, 8 relay outputs, 4 analog inputs and 2 analog outputs. The number 22 represents this total, rather than 22 digital inputs. There are no built-in Pt100 inputs. For pressure, level or speed-reference applications, check the sensor’s electrical output together with the scaling in the machine program.

Analog input and output specifications

Analog inputs offer ±10 V at 12 bits or ±20 mA at 11 bits. The two analog outputs provide ±10 V or 0–20 mA at 12 bits. Analog isolation is not provided.

Voltage and current connections require different treatment. For 4–20 mA measurement, match the channel mode, transmitter supply and lower/upper scaling values. Monitoring the PLC’s raw reading separately from the displayed engineering value helps distinguish wiring problems from scaling errors. Use the relevant channel wiring diagram when changing signal connections.

Digital I/O and relay loads

Relay resistive-load limits are 1.5 A per point and 5 A per COM; switching-voltage limits are 250 V AC / below 30 V DC.

Calculate the load on each output and the total common-group current separately. Contactor and valve coils also require attention to inrush current and suitable suppression. On the input side, check the sensor’s PNP/NPN arrangement together with the input-common wiring. Review the load circuit before substituting a transistor-output model for a project designed around relays.

Cabinet dimensions and mounting

Overall dimensions are 175.8 × 108.6 × 59.2 mm. The mounting drawing specifies a cutout range of 162.7–164.0 × 95.5–97.0 mm and panel thickness of 0.5–5 mm.

When planning mounting and power connections, allow access to the rear terminals, cable bends, gasket and fixing parts. Compare an existing cabinet opening with the mounting drawing; the front-frame dimensions alone do not establish a suitable fit.

Communication and project backups

USB is used for program transfer, and both serial channels use RS-485. COM2 serves PLC mode; COM3 serves panel mode. Panel-mode communication can depend on the active screen page, so check what happens to data exchange when the screen changes. Select programming and connection cables and communication peripherals for the actual port duty.

Consider TPEditor for the screen project and WPLSoft or, after verifying target support, ISPSoft for the PLC. Choose Delta PLC software versions to match the existing project, and retain separate screen and PLC backups. Access to the screen does not establish that the PLC program has also been backed up.

Model comparison and selection

TP04P-16TP1R and TP04P-32TP1R are digital-I/O alternatives. Review TP04P-21EX1R separately for temperature measurement and a different analog-channel arrangement. For a colour touchscreen, compare TP70P-22XA1R in the Delta TP70P family. Verify mechanical dimensions, project support and terminal compatibility before treating any of these models as a direct replacement.

Editor’s Note

Read the full 22XA1R code before buying. A matching TP04P enclosure alone does not establish that the required analog channels are present. Ask for clear photographs of the rear nameplate and terminals.

Do more than connect one sensor and look for a number on the screen. Test every analog input at low, middle and high points with a suitable calibrator. For a 4–20 mA application, check 4, 12 and 20 mA, recording both raw and displayed values.

Disconnect the machine load before testing each analog output with suitable instruments and a test load. Distinguish voltage output from current output; avoid sending arbitrary test references to a connected drive. Remove power before changing terminal wiring.

Check every key, particularly frequently used ENTER and direction keys, for intermittent operation. Inspect contrast, backlighting and readability after the unit has warmed up. The physical keypad is an essential part of operating this panel.

An unstable reading does not immediately establish an analog-board fault. Check transmitter power, reference wiring, AG/FE connections against the diagram, and signal-cable routing near power conductors. Disconnect the field circuit and compare the result with a clean test signal first.

Obtain both screen and PLC backups before erasing a project from a working machine. A clicking relay does not prove that its contacts are sound; have outputs tested under a suitable load. Confirm whether terminals, fixing parts and existing project files are included.

PDFs and technical documents

Start with the Delta TP panel files page. In the TP04P sheet, TP-014CB30-01, 6 September 2022, printed page 2 covers mounting, page 3 electrical limits and page 4 analog specifications. These are the document’s printed page numbers. Explore Delta PLC and HMI manuals for other document groups.

Related topics

Explore the Delta PLC family and Delta PLC accessories for other controllers and connection options. Browse used Delta equipment for listed units and Second Hand Models for other brands. Confirm the complete model code, condition and included items with the store responsible for the listing.

External references

Delta TP04P manufacturer instruction sheet — English/Chinese, 6 September 2022. This Mouser-hosted copy includes a distributor appendix on its final page.