Delta TP70P-22XA1R
Delta TP70P-22XA1R Touch Panel with Built-in PLC
Delta TP70P-22XA1R combines a 7-inch, 800 × 480-pixel touchscreen, a built-in PLC and mixed I/O in one enclosure. It provides 8 digital inputs, 8 relay outputs, 4 analog inputs and 2 analog outputs. This Delta TP70P variant suits applications requiring analog measurements and reference signals alongside digital control.
A project may combine pressure or level transmitter monitoring, touchscreen setpoint entry and an analog speed reference to a suitable drive. Although listed under Delta TP panels and remote I/O, this device has its own PLC logic and local I/O. Its built-in I/O count cannot be increased by attaching expansion modules. Communication with other devices must be planned separately from physical I/O expansion.
Power supply, display and digital I/O
The supply is 24 V DC, PLC program capacity is 4k steps, and the panel cutout is 191 × 128 mm. Check rear connection clearance and gasket seating before installation. Related installation information is available under Delta HMI mounting and power connections.
X0–X7 accept 24 V DC digital signals; the instruction sheet specifies an input current of 5 mA. Connect the S/S0 common to suit the required sink/source arrangement. Y0–Y7 relay outputs use common terminal C0. The sheet lists contact ratings of 250 V AC or below 30 V DC, 1.5 A; also observe load type and common-terminal limits. Relay outputs must not be treated as transistor pulse outputs.
Analog channels and PLC registers
The analog section has 4 inputs and 2 outputs; the instruction sheet specifies 12-bit resolution and 3 ms conversion time per channel. Input modes are −10…+10 V, −20…+20 mA or 4…20 mA; output modes are −10…+10 V, 0…20 mA or 4…20 mA.
D1110–D1113 hold analog input values; D1115 selects channel modes; D1116–D1117 command analog outputs. D1115 fields are AD0: bits 1–0, AD1: 3–2, AD2: 5–4, AD3: 7–6, DA4: 9–8, DA5: 11–10. 4–20 mA inputs use 0–1000; 4–20 mA outputs use 0–4000.
Do not assume that every channel uses 0–4095 simply because the hardware is specified as 12-bit. Check transmitter engineering units, channel mode and PLC scaling together. Follow the model-specific wiring diagram for voltage/current terminals, required current-input links and analog commons.
Programming and communication
Create the operator interface with Delta TPEditor. Program the PLC logic using Delta WPLSoft or Delta ISPSoft after checking model support. Keep backups of both projects. USB is used for program transfer, and COM2 and COM3 provide RS-485 communication.
The model's DB9 pin definition identifies COM2/PLC D+ on pin 6 and D− on pin 7; COM3/TP D+ on pin 8 and D− on pin 9; GND on pin 5. Confirm connector orientation from the drawing. When consulting Delta PLC cables and HMI programming and HMC cables, select the cable by electrical interface and pinout. Match port function, station address and serial settings to the existing project.
Differences from related models
TP70P-16TP1R provides 8 digital inputs and 8 relay outputs, while TP70P-32TP1R provides 16 digital inputs and 16 relay outputs. The 22XA1R adds four analog inputs and two analog outputs. TP70P-21EX1R has a different arrangement: 2 analog inputs, 1 analog output and 2 Pt100 inputs. These variants do not have interchangeable I/O configurations.
TP04P-22XA1R offers the same I/O counts with a smaller, different display and mounting arrangement; compare the screen project and panel cutout separately. When considering TP70P-RM0, check the requirement for existing local I/O separately. Matching screen size alone does not establish replacement compatibility.
Editor's Note
When buying a used TP70P-22XA1R, go beyond checking whether the screen lights up. Test the touchscreen corners, page changes and backlight. Read the complete model code on the label; a similar front panel is not enough to identify the hardware.
Back up both the screen project and PLC program first. If the installed panel is your only working copy, confirm that the project can be recovered or reloaded before attempting an update. Keep that working copy safe while investigating the fault.
Test analog inputs at low, middle and high points with a calibrator. For a channel configured for 4–20 mA, apply 4, 12 and 20 mA and compare the raw reading with the displayed engineering value. If they disagree, check mode, wiring and scaling before condemning the analog circuitry.
Disconnect the field load before testing an analog output and use a suitable meter or test load. Match the selected output range to the receiving device. Bench measurements give a clearer diagnosis than uncontrolled tests with a drive still connected.
A clicking relay does not prove that its contacts are healthy. Check every output with a light test load. Investigate terminals, common wiring and the supply before deciding that the relay has failed. Use suitable suppression for inductive loads such as contactor coils.
For intermittent communication, check the pinout, D+/D− wiring and project settings methodically. Measure the supply under load, inspect terminals for corrosion and check whether analog wiring runs beside power cables. These checks make the eventual repair decision much more reliable.
Sources and PDF files
Series document page: Delta TP panel files. Other documents can be found under Delta PLC and HMI manuals. Use TP70P Quick Start, section 3.9 for analog channel configuration and the TP70P-22XA1R instruction sheet for terminal and connector definitions.
Related topics
Delta DVP PLC series · Delta PLC accessories · Delta HMI modules and accessories · Delta HMI communication peripheral units · Delta HMI files · Delta user manuals
Navigation: TP70P overview · TP panels and remote I/O · Delta PLC models · Second-hand Delta products
External references
Delta TP70P-22XA1R instruction sheet, 15 June 2022 (multilingual, including Turkish and English) · Delta TP70P Quick Start, 6 October 2022 (English)