Delta TP04P-21EX1R
Delta TP04P-21EX1R Keypad Operator Panel with Built-in PLC
Delta TP04P-21EX1R combines a 4.1-inch, monochrome 192×64-pixel STN-LCD, physical keys and a built-in PLC. This Delta TP04P model provides 8 digital inputs, 8 relay outputs, 2 analogue current inputs, 1 analogue current output and 2 Pt100 temperature inputs. Operator commands are entered through the keypad rather than a touchscreen.
It can combine temperature monitoring with current signals from pressure, level or flow transmitters. The PLC program handles setpoint entry, analogue references to compatible drives and auxiliary equipment control. Within Delta TP panels and remote I/O, it is a panel with local I/O that executes its own program.
Power supply, PLC capacity and installation
The nominal supply is 24 V DC; the instruction sheet lists 4.2 W power consumption. The TP04P installation sheet specifies 8k steps of PLC program capacity. Overall dimensions are 175.8×108.6×59.2 mm, with a nominal 163×96 mm panel cutout. Check exact cutout tolerances and panel thickness against the drawing. HMI mounting and power connections provides further installation references.
Digital inputs and relay outputs
X0–X7 are 24 V DC digital inputs. Check the sensor’s PNP/NPN arrangement together with the S/S0 common. Y0–Y7 relay outputs use common terminal C0. Resistive-load limits are 1.5 A per point and 5 A total per common; contact voltage is 250 V AC or below 30 V DC.
The common-terminal limit prevents all eight outputs from simultaneously carrying 1.5 A each. Contactor and valve coils require suitable suppression and, where necessary, an interposing relay. Relay outputs are not servo pulse-command or fast PWM outputs.
Analogue current channels and PLC addresses
The two current inputs and single current output handle 0–20 mA or 4–20 mA with the appropriate channel configuration. The 2022 sheet specifies 12 bits, 5 µA per step and a 0–4000 digital scale for this model’s current channels. In 4–20 mA mode, 4 mA is the lower measurement point and 20 mA the upper point; configure the screen’s engineering scale separately.
D1110/D1111 hold current-input values, D1112/D1113 hold Pt100 temperatures and D1116 controls the current output. The TP programming manual identifies D1114 as the TP04P analogue-channel mode register. Do not directly copy the TP70P’s D1115 setting into this model.
Pt100 inputs and documentation differences
The temperature channels accept 2-wire or 3-wire Pt100 sensors. The manufacturer’s 2022-09-06 sheet specifies −20…+300 °C, a −200…3000 digital range and 0.1 °C increments. Older TP04P sheets also show −20…+160 °C; verify the supported range against the documentation and version information for the actual unit.
A temperature value of 250 represents 25.0 °C. Display increments and total measurement accuracy are different specifications. Do not connect a thermocouple, 0–10 V signal or current-transmitter output to a Pt100 terminal. Apply any two-wire bridge only as shown in the relevant wiring drawing.
Programming, backups and communication
Use Delta TPEditor for screen pages and key functions, and Delta WPLSoft or Delta ISPSoft with the appropriate target for PLC logic. The 2022 sheet also lists DIAScreen among the screen tools; check support for the existing project and model. Back up the screen project and PLC program separately.
Program transfer uses USB Type-B / virtual COM. Field communication uses COM2 and COM3 RS-485. When selecting Delta PLC cables or HMI programming and HMC cables, verify connector type, pinout and port function together. Delta COMMGR provides an additional connection reference.
Station address, baud rate, parity and the data map must match the connected device. The program-copy card slot is not a physical I/O expansion slot; reading external equipment through serial communication requires a separate system arrangement.
Differences from nearby models
TP04P-16TP1R provides 8 inputs/8 relay outputs; TP04P-32TP1R provides 16 inputs/16 relay outputs. TP04P-22XA1R has 4 analogue inputs and 2 analogue outputs for voltage/current signals. The 21EX1R combines current channels with two dedicated Pt100 inputs.
TP70P-21EX1R offers similar channel counts with a 7-inch colour touchscreen. Assess the TP70P family separately for display, installation and project differences. The transistor-output TP04P-21EX1T is also not a replacement for the relay 21EX1R with unchanged field wiring.
Editor's Note
Start by testing the keys. Intermittent Enter, arrow or numeric keys can make the panel frustrating to operate. Check contrast and backlighting too; a lit display does not prove that the complete unit is healthy.
Before removing a working panel, save the screen and PLC backups separately. Record analogue modes, display scaling and communication settings. If the source project is missing, establish what can be read from the device before downloading a replacement program.
Check the current inputs at several points using a suitable calibrator. When applying 4, 12 and 20 mA, confirm whether the selected mode is 4–20 mA or 0–20 mA; the same signal can produce different digital values. Check raw values and scaling before blaming the analogue hardware.
Compare both Pt100 inputs under identical conditions with a suitable simulator or verified sensor. Documentation versions give different upper limits, so establish the unit’s supported range rather than assuming it. Check sensor wiring, the two/three-wire arrangement and terminal contacts; never apply 24 V randomly to analogue terminals.
A clicking relay does not establish healthy contacts. Disconnect the field circuit and test outputs individually with a suitable low-voltage load, including the C0 common connection. Measure the analogue output on a compatible test load as well; a displayed command is not proof of a correct output signal.
For intermittent resets or jumping readings, check the loaded 24 V supply, loose terminals and separation between signal and power wiring first. During repair, assess the supply, relay stage and analogue section separately. Verify all channels under controlled conditions before returning the machine to service.
Manuals and PDF files
Start with the relevant documents in Delta TP panel files. Use Delta PLC and HMI manuals and Delta HMI Files for broader document selection. Alongside the installation sheet, use programming tables that explicitly cover TP04P and the 21EX1R model.
Related topics
Delta DVP PLC series · Delta HMI Modules and Accessories · Delta HMI Communication Peripheral Units · Delta PLC accessories
Navigation: TP04P main page · Delta PLC section · Delta user manuals · Used Delta products
External references
Delta TP04P instruction sheet — 2022-09-06, includes English; manufacturer PDF hosted by Mouser · Delta TP programming manual — analogue register and mode table, English