Delta TP04P-16TP1R

Delta TP04P-16TP1R Keypad Operator Panel with Built-in PLC

Delta TP04P-16TP1R combines a 4.1-inch STN-LCD, monochrome 192 × 64-pixel display, physical keys and a built-in PLC. It provides 8 digital inputs and 8 relay outputs. This Delta TP04P model processes local digital signals while allowing the operator to view machine status and enter values through the keypad.

The PLC project can process pushbuttons, limit switches and suitable digital sensors, and control contactors or auxiliary relays through appropriately selected interface devices. The 16TP1R has no built-in analog inputs, analog outputs or Pt100 inputs. Preserve this distinction when selecting equipment under Delta TP panels and remote I/O.

Power supply, display and installation

The nominal supply is 24 V DC. The model instruction sheet lists 3.2 W consumption and dimensions of 175.8 × 108.6 × 59.2 mm. The nominal panel cutout is 163 × 96 mm; check mounting tolerances and panel thickness against the drawing. Allow rear terminal clearance and seat the gasket and mounting brackets correctly. See Delta HMI mounting and power connections for related installation topics.

Operator commands use numeric, direction and function keys. The project can display setpoints, counters, operating states and configured alarms. Consider the Delta TP70P family separately when a touchscreen interface is required.

Digital inputs and relay outputs

X0–X7 accept 24 V DC digital signals. The sheet specifies 5 mA input current; connect common terminal S/S0 to suit the required sink/source arrangement. X0 and X1 support 10 kHz high-speed inputs. This rating does not apply indiscriminately to every input.

Y0–Y7 relay outputs share common terminal C0. The sheet specifies 1.5 A per point and 5 A total per common for resistive loads, with contact voltage ratings of 250 V AC or below 30 V DC. Loading all eight outputs at 1.5 A simultaneously would exceed the common-terminal rating. Observe the applicable inductive-load limits and use suitable suppression.

Relay outputs are not high-speed pulse outputs. Reading fast signals through X0/X1 does not establish that the Y outputs can generate pulses at the same rate. Select output technology separately for servo pulse commands or frequent switching.

PLC capacity, programming and communication

The TP04P instruction sheet and manufacturer series catalog specify 8k steps of PLC program capacity. The 1 MB Flash specification describes a different memory quantity. Check project size and hardware/software compatibility together when replacing a unit.

Create screen pages and key functions with Delta TPEditor. Use Delta WPLSoft or Delta ISPSoft with confirmed model support for PLC logic. The screen project and PLC program require separate backups. Retain software versions and communication settings with those backups.

Program transfer uses USB Type-B through a virtual COM port. COM2 and COM3 provide RS-485; the series description lists Modbus ASCII/RTU support. Match port function, station address, baud rate and parity to the project. When selecting Delta PLC cables and HMI programming and HMC cables, verify the electrical interface and pinout.

The built-in 8 inputs and 8 outputs cannot be increased by attaching standard PLC expansion modules. Exchanging data with other devices over communication requires a separate system design. The program copy-card slot is not a physical I/O expansion slot.

Differences from related models

TP04P-32TP1R provides 16 digital inputs and 16 relay outputs. Consider TP04P-22XA1R for analog I/O and TP04P-21EX1R for analog current and Pt100 measurement. The family's transistor-output TP04P-16TP1T must not be treated as a replacement requiring no field-wiring changes.

TP70P-16TP1R also provides 8 digital inputs and 8 relay outputs, but uses a 7-inch color touchscreen and a different mounting arrangement. Matching I/O counts do not establish direct screen-project or panel-cutout compatibility.

Editor's Note

Start by testing the keys. Intermittent Enter, direction or numeric keys can make an otherwise working machine difficult to operate. Check contrast, backlight and readability across the display as well.

Back up both the screen project and PLC program before removing a working unit. Finding the screen file alone is not enough. If source files are missing, confirm what can be uploaded and reloaded before downloading a replacement program.

During bench testing, activate every input in turn and monitor its PLC address. Check the actual register or input state rather than relying only on an indicator. Establish the S/S0 common arrangement before applying a test signal.

A relay click does not prove that its contacts are healthy. Test Y0 through Y7 with a light load and inspect C0, common wiring and loaded output behavior. A faulty common connection can resemble several failed outputs.

For intermittent resets, measure the 24 V supply under load first. Loose terminals, corrosion or a voltage dip when a contactor operates can produce similar symptoms. Once the supply is verified, inspect the board for contamination, overheating and damaged connections.

Read the final letter when selecting a replacement: relay R and transistor T versions have different output arrangements. Photograph the label and terminals before disconnecting the original unit. That small preparation can save considerable time during recommissioning.

Sources and PDF files

Use Delta TP panel files for series documents and Delta PLC and HMI manuals for other technical references. Base terminal wiring on an instruction sheet explicitly covering TP04P-16TP1R, and check program copying and communication procedures against the software version in use.