Delta DVP16XN211R

Delta DVP16XN211R – 16-point relay output expansion module

Delta DVP16XN211R adds 16 relay outputs and 0 digital inputs to DVP-ES2 and DVP-EX2 PLC systems. Delta also lists it in its DVP-ES3 and DVP-EX3 documentation. Check the I/O capacity and expansion order for the exact host CPU. Related pages include DVP-ES3, DVP ES2 / EX2 modules and DVP expansion modules.

24 V DC supply and relay load ratings

Apply nominal 24 V DC auxiliary power to the module’s 24V and 0V terminals. C0, C1 and C2 are the load circuit commons. Delta gives different upper supply tolerance limits in its two documents. Follow the nameplate and hardware documentation for the installed revision.

Delta’s module manual specifies 10–250 V AC or 5–30 V DC, 2 A per output and 5 A per common for resistive loads. Relay response is approximately 10 ms and the stated switching limit is 1 Hz. Check inrush, load type and contact life for solenoids, contactor coils and lamps. Mechanical relays suit ordinary on/off switching.

The physical terminal groups are C0 → Y0–Y3, C1 → Y4–Y7 and C2 → Y10–Y17. Where all eight C2 loads can be active together, their combined current must stay within the 5 A common limit. See section 2.5.7 of the module manual for the wiring diagram.

Addressing, programming and cable

The terminal labels span Y0–Y17. Actual program addresses depend on the host CPU and preceding modules. Delta’s DVP32ES200R → DVP08XP211R → DVP16XP211R → DVP16XN211R example assigns Y40–Y57 to the final module. DVP uses octal I/O numbering.

The host CPU holds the program. Use WPLSoft or ISPSoft for the ES2/EX2 CPU. Delta lists UC-PRG020-12A or the UC-MS020-01A serial cable for the CPU’s COM1 (RS-232) connection. In ISPSoft, COMMGR can manage the connection.

Delta’s 2024 programming manual lists ISPSoft or DIADesigner for ES3 and DIADesigner for ES300TEC and EX3. A USB data cable to the CPU is a connection option for these models.

Related models and topics

Compare DVP08XN211R for eight relay outputs, DVP16XN211T for 16 transistor outputs, DVP16XP211R for eight inputs and eight relay outputs, and DVP24XN200R for 24 relay outputs with an AC supply. The legacy ES/EX DVP16XN11R has a similar code. Check the series, supply and terminal layout before replacement.

Input expansions include DVP08XM211N and DVP16XM211N. Mixed I/O options include DVP08XP211R, DVP16XP211T, DVP24XP200R and DVP32XP200R.

Editor’s Note

Look for the full 211R suffix on a used unit and confirm that its removable terminal blocks are present.

A relay click is only a starting point. Test all 16 outputs with a suitable load and check each of the three common groups.

If the LED lights and the load stays off, check the group supply and fuse, then measure voltage drop across the closed contact under load.

If the load remains on after the command goes off, check the field wiring and consider a welded relay contact.

For repeat failures, check inrush and coil suppression before replacing another relay. Isolate machine power before servicing.

PDF documents and navigation

Delta DVP PLC PDF files · DVP16XN211R · Delta PLC · Delta main page

External references · ES2 DIDO instruction sheet (2024, EN/Chinese) · ES2 DIDO instruction sheet (2011, includes Turkish) · DVP Module Manual (EN)