Delta DVP08XP211R
Delta DVP08XP211R — 4 Digital Inputs, 4 Relay Outputs
Delta DVP08XP211R is a mixed I/O expansion module that adds four 24 V DC digital inputs and four relay outputs to DVP-ES2 and DVP-EX2 PLC systems. The CPU expansion bus supplies the module’s 24 V DC operating power. Delta’s ES2 instruction sheet lists 1.2 W consumption. Include this load in the CPU’s expansion power budget.
Digital inputs and the S/S common
The input terminals are X0–X3, with S/S as their common. Each input is rated for 24 V DC and approximately 5 mA. The ON threshold is >15 V DC and the OFF threshold is <5 V DC. Response is 10 ms from OFF to ON and 15 ms from ON to OFF, both with a ±10% tolerance.
For NPN sensors, connect S/S to +24 V. For PNP sensors, connect S/S to 0 V. Select the sensor wiring arrangement for all four inputs because they share S/S. Applications include inductive sensors, photoelectric sensors, limit switches and pushbuttons. Terminals marked NC are unused.
Relay outputs and the C0 common
The four normally open relay contacts at Y0–Y3 share one C0 common. An external source powers the loads. Delta’s wiring section for this model gives 10–240 V AC or 5–30 V DC. The resistive load limits are 2 A per output and 5 A at C0. Four 1.5 A loads operating together draw 6 A and exceed the common limit.
Use one load supply for the entire C0 group. For coils, check inrush, switching frequency and the contact life curve. Select suitable fuse protection and coil suppression. Use a suitably rated contactor to switch motor power. The manual lists approximately 10 ms relay response and a switching frequency of up to 1 Hz.
Address allocation and host selection
In Delta’s instruction-sheet example, DVP08XP211R is the first extension after a DVP32ES200R CPU and uses X20–X23 and Y20–Y23. The four physical inputs and four physical outputs each reserve an eight-address block. In the same example, the next 8-input/8-output module starts at X30 and Y30. Check live addresses when the CPU or expansion order changes.
Check host I/O capacity and the power budget for ES2/EX2 modules. Delta’s module manual also covers DVP-ES3 and EX3 systems. For those systems, check the expansion table for the exact host CPU.
Programming software and cable
The host PLC program reads and writes the module’s I/O. Use WPLSoft or ISPSoft as supported by the ES2/EX2 CPU to edit the ladder program and monitor the X/Y addresses.
Delta’s cable guide lists UC-PRG020-12A for the ES2/EX2 CPU’s 8-pin mini-DIN RS-232 COM1 port. UC-MS020-01A is the serial option and can be used with a USB-to-RS-232 converter if needed. Select the COM port assigned by the USB driver. For ISPSoft, configure COMMGR for the host CPU.
Editor’s Note
Read the full 211R suffix before you buy. The DVP08XP211T also has four inputs and four outputs, but uses NPN transistors. On the relay model, trace C0 and the Y terminals when checking the panel wiring.
On a used unit, examine the removable terminals and the side expansion connector first. Darkening, melting or a loose screw around C0 also warrants a check of the load circuit.
Test the inputs one at a time with a suitable 24 V signal. Check both the input LED and the actual X address in the CPU monitor. Incorrect S/S polarity can make all four inputs appear faulty.
Test each C0–Y contact with a suitable small DC load and appropriate protection. If the load stays on with the Y command off, check for a welded contact. If the LED is on and the load stays off, measure the C0 supply and the voltage drop across the contact.
After testing the first four addresses, check where the next module starts. Counting only physical terminals can send you looking for the next channel at X24 or Y24.
PDF documents
See Delta DVP PLC files for the terminal diagram, the address allocation example and CPU cable selection. See section 2.5.4 of the module manual and I/O Point Serial Sequence in the instruction sheet for model-specific details.
Related models
DVP08XN211R provides eight relay outputs, DVP08XM211N provides eight digital inputs, and DVP16XP211R provides eight inputs and eight relay outputs. DVP24XP200R provides 16 inputs and eight relay outputs with its own AC line supply. For DVP08XP11R from the earlier ES/EX generation, check the host family and terminal layout separately.
Related topics and navigation
DVP08XP211R main page · DVP expansion modules · Delta DVP PLC series · Delta PLC models · Second-hand Delta products
External references
Delta DVP Module Manual (2026, EN) · ES2 Digital I/O Instruction Sheet (2024, EN/ZH) · Delta PLC/HMI Cable Selection Guide (2019, EN)