Delta DVP24XN200R

Delta DVP24XN200R – AC-Powered Expansion Module with 24 Relay Outputs

Delta DVP24XN200R is a 100–240 V AC expansion module with 24 relay outputs and no digital inputs. It belongs to the DVP-ES2 / EX2 module family and is also listed for DVP-ES3 in the manufacturer’s 2023 catalogue. It increases the output capacity of a PLC main unit; it has no independent CPU or user program.

Typical applications include lamps, interposing relays and suitable coil loads in packaging machines, conveyors and auxiliary control circuits. When selecting PLCs and accessories, read the complete 24XN200R code. On this model, 24 refers entirely to outputs. In terms of digital and analogue signals, it provides switched contacts rather than analogue measurement or sensor inputs.

Main supply and auxiliary 24 V output

Connect the main supply to L and N: 100–240 V AC, 50/60 Hz. The instruction sheet specifies a voltage tolerance of −15% / +10%, frequency tolerance of ±5% and 20 VA power consumption for this model. Connect the protective earth terminal to the cabinet grounding system.

+24V and 24G are auxiliary DC output terminals, not main supply inputs. The DVP24XN200R group is rated for 100 mA from this output. It should not be treated as a power supply for all field loads. If an external DIN-rail power supply is required, design the field supply arrangement separately and do not casually parallel it with the auxiliary output.

Relay contacts and common terminal groups

The outputs use mechanical relay contacts. The module manual specifies 10–250 V AC or 5–30 V DC contact operation, with resistive load limits of 2 A per output and 5 A per common. There are six commons, each shared by four outputs:

C0: Y0–Y3   |   C1: Y4–Y7   |   C2: Y10–Y13.
C3: Y14–Y17   |   C4: Y20–Y23   |   C5: Y24–Y27.

For example, four simultaneous 1.5 A loads on one common total 6 A, exceeding the 5 A group limit. Checking only the individual channel rating is insufficient. For inductive loads such as contactor coils, assess inrush current and contact life separately. Choose any interposing relay and socket and fuse to suit the load circuit.

The instruction sheet lists lamp loads of 20 W DC / 100 W AC and provides separate life curves for inductive loads. Relay switching is limited to 1 Hz maximum, with an approximate 10 ms response time. This relay model should therefore not be selected for fast pulses, PWM or stepper pulse trains.

Terminals and output addressing

NC terminals are unused, no-connection terminals. They are not normally closed relay contacts. C0–C5 are the output group commons. There are no X inputs or S/S input common on this module; do not connect sensors to unused terminals.

Local output labels are Y0–Y7, Y10–Y17 and Y20–Y27, using octal numbering. These labels are not automatically the absolute CPU program addresses. For example, if this is the first output expansion after a DVP32ES200R, with no preceding output module, ES2 addressing assigns Y20–Y47. Local Y0 → Y20, Y7 → Y27, Y10 → Y30 and Y27 → Y47. Recalculate the starting address for a different CPU or module sequence.

Programming software and connection cable

DVP24XN200R is not programmed directly. The application runs in the DVP-ES2 or DVP-EX2 main unit. Select a supported CPU in WPLSoft or ISPSoft; configure COMMGR for an ISPSoft connection. In the ladder diagram, output instructions must use the actual system Y addresses.

For a standard ES2/EX2 CPU’s COM1 RS-232 port, the manufacturer’s cable guide shows UC-PRG020-12A for USB connection and UC-MS020-01A for a computer with an RS-232 port. Install the appropriate USB cable driver and select the correct COM port in the software. Connect to the CPU rather than the expansion module.

An ES3 main unit uses DIADesigner. Choose its connection port and cable from that ES3 CPU’s manual; do not apply the ES2 serial cable arrangement to every ES3 model. Check supported expansion capacity and hardware configuration against the actual host CPU.

Differences from related models

DVP24XN200T has 24 transistor outputs and cannot replace the relay version using unchanged wiring. DVP24XP200R provides 16 digital inputs and 8 relay outputs, while DVP32XP200R provides 16 digital inputs and 16 relay outputs. DVP08XN211R is an 8-relay-output candidate for smaller requirements. Compare supply, commons and host CPU conditions separately; these are selection alternatives rather than guaranteed direct replacements.

Related topics and application notes

Inductive sensors, photoelectric sensors, limit switches and pushbuttons connect to the CPU or a suitable input module. DVP24XN200R does not read them; it executes the program’s output commands. Sink/source selection concerns input or transistor circuits and does not make this module’s relay contacts NPN or PNP outputs.

Separating coil and mains wiring from low-level signal wiring helps control electromagnetic interference. When choosing panel components, consider terminal access, wire sizing, circuit protection and heat dissipation together.

The PLC program can implement timer functions or commands based on counter results. Manual commands from an HMI panel should pass through the same interlocks. A visible software command alone does not prove that a relay contact is healthy under load.

Editor’s Note

Start with a clear label photograph showing DVP24XN200R. Differences between XN and XP, 200 and 11, or R and T change the required wiring. Ask for photographs of the terminal cover and side expansion connector as well.

Check all 24 channels before calling a used module healthy. Inspect for burning, loose terminals and corrosion with power isolated, then use a safe test load to check each common and its four outputs. Mains-side measurements require suitable equipment and qualified personnel.

An illuminated LED and an audible relay click are not enough. Worn contacts can pass an unloaded check yet drop voltage or stick under load. Observe contact behaviour with an appropriate test load and avoid uncontrolled output forcing that could move the machine.

If all four outputs in one group fail together, inspect the common supply, fuse and terminal first. For a single faulty channel, examine the relay, solder joints and copper path separately. A replacement relay must match coil voltage, pin arrangement and contact rating.

Suitable suppression near a coil can improve contact life. For DC coils, consider diode polarity and release delay; for AC coils, select an appropriate RC network or MOV for the application. Increasing the fuse rating does not fix a recurring fault.

When buying used equipment, assess the main supply and the 100 mA auxiliary output separately. Measuring 24 V does not establish that all relay channels work. Recording the host CPU, module sequence and tested channels makes later maintenance easier.

PDF manuals and technical documents

Use our Delta DVP PLC files page for the series manuals and collected documents. This model package contains the 2024 DVP-ES2 DIDO instruction sheet, DVP module manual (1st edition, 2023), 2023 DVP/TP catalogue and 2019 PLC/HMI cable selection guide. The instruction sheet has English and Chinese sections plus French safety warnings; the other three documents are in English. The cable information applies to the host CPU.