Delta DVP08XN211R
Delta DVP08XN211R – 8 Relay Output PLC Expansion Module
Delta DVP08XN211R adds eight digital relay outputs to a PLC CPU system. This DVP expansion module provides 0 inputs and 8 outputs for panel indicators, interposing relays and suitably rated coils. Delta’s selection catalogue lists it with the DVP-ES2, DVP-EX2 and DVP-ES3 expansion modules.
Supply, contact ratings and switching
The CPU expansion bus supplies the module with 24 V DC. An external circuit supplies the load voltage switched by the dry relay contacts. The detailed table and DVP08XN211R wiring diagram in the 2026 module manual specify 10–240 V AC or 5–30 V DC. The selection table in the same manual lists 250 V AC, so this page follows the wiring diagram’s 240 V AC upper limit.
The resistive load ratings are 2 A per output and 5 A per common. Four outputs drawing 2 A each would put 8 A through one common. Include the total group current in your fuse and load calculations. Delta specifies about 10 ms relay response and a 1 Hz switching limit. For high-speed pulses, check the specifications of the CPU or a suitable transistor output.
C0 and C1 wiring
Top row C0 · Y0 · Y1 · Y2 · Y3 · NC. Bottom row C1 · Y4 · Y5 · Y6 · Y7 · NC. C0 serves the first four channels and C1 serves the last four. Each Y terminal switches the load voltage applied to its group’s common. Leave the NC terminals unused.
Use the same voltage for all loads sharing a common. Check the terminal order, field fuses, cable routing and cabinet grounding against the wiring diagram. Isolate power before checking the 35 mm DIN rail mount and expansion connector.
Addressing, software and cables
Y0–Y7 are the module’s terminal markings. The actual Y addresses depend on the host PLC outputs, expansion order and CPU addressing rules. Compare the I/O module layout with the Y addresses in the project. The host CPU controls DVP08XN211R and receives the PLC program.
For an ES2/EX2 CPU, use WPLSoft or a compatible release of ISPSoft. The UC-PRG020-12A USB-to-RS-232 cable connects to the CPU’s COM1 RS-232, 8-pin mini-DIN port. Install the USB serial driver and select its virtual COM port. The UC-MS020-01A serial cable suits a computer with a physical RS-232 port.
For a standard ES3 CPU, use ISPSoft or DIADesigner. Connect a USB data cable to the CPU’s Mini-B port and install the appropriate USB driver. Select software for the exact CPU order code and project version.
Related models
DVP08XN211T provides eight NPN transistor outputs, DVP08XP211R provides four digital inputs and four relay outputs, and DVP16XN211R provides 16 relay outputs. DVP24XN200R has 24 relay outputs and a 100–240 V AC operating supply. Compare the supply and common terminals on the model diagrams before replacement.
Editor’s Note
On a used module, check the 211R label and expansion connector first. Darkened terminals and loose screws can cause faults under load.
Contacts can be worn even when the LED lights and the relay clicks. Test each Y terminal against its own C terminal with a suitable low-voltage test load.
If four outputs fail together, begin troubleshooting with the C0 or C1 supply and the group fuse.
Account for coil inrush and turn-off voltage spikes. Consider an appropriately oriented diode for a DC coil or a suitably rated RC suppressor for an AC coil.
Frequent switching shortens relay life. For high-current or frequently switched loads, select a suitable SSR or interposing relay and check its control load.
Clear output forces before returning to automatic operation. Verify emergency stop circuits against the machine safety design.
PDF manuals and related topics
Delta DVP PLC files · See DVP Series Module Manual §2.5.2, printed page 2-10 for model wiring and §2.6.2 for relay output circuits and load information.
Related topics · Digital and analogue signals · PLC programming languages
Navigation · Delta Automation · Delta PLC · DVP series · ES2/EX2 modules
External references
Delta module manual, 6 January 2026 (EN) · DVP selection catalogue, 3 January 2023 (EN) · PLC/HMI cable guide, 15 August 2019 (EN)