Delta DVP08XM211N

Delta DVP08XM211N – 8-Point Digital Input Expansion Module

Delta DVP08XM211N adds eight 24 V DC digital inputs to a compatible PLC CPU. It has zero outputs and local inputs X0–X7. It belongs to the DVP-ES2/EX2 expansion module family. Delta’s DVP-E module and CPU documentation also covers DVP-ES3 and DVP-EX3 connections.

Use it to add inductive sensors, capacitive sensors, photoelectric sensors, limit switches or pushbuttons. Check the signal type when choosing between analogue and digital inputs. This module reads on/off states. Sensors that report a measured value as 0–10 V or 4–20 mA require an analogue input module.

Power and input ratings

The CPU supplies module electronics through the expansion bus. The ES2 DIDO sheet lists module consumption at 1.2 W. Plan the 24 V DC field supply for the sensors separately and check the host CPU manual for its expansion power budget. If using a separate 24 V DC panel power supply, include the S/S reference in the field wiring diagram. Select the fuse for the field branch and cable.

Each input draws 5 mA at 24 V DC and has 4.7 kΩ input impedance. Delta specifies an ON threshold above 15 V DC and an OFF threshold below 5 V DC. Hardware response times are 10 ms ON and 15 ms OFF, both with ±10% tolerance. For fast encoder pulses, use a supported high-speed counter input on the CPU. The module is 45 mm wide and mounts on a 35 mm DIN rail.

S/S common and PNP/NPN wiring

For a PNP sensor, connect S/S to 0 V. Connect the sensor output to the desired X input. The output supplies +24 V when active. For an NPN sensor, connect S/S to +24 V. Connect the sensor output to the desired X input. The output pulls the input to 0 V when active. Delta calls the PLC input sinking for PNP and sourcing for NPN. Check the S/S connection when choosing the sink/source wiring arrangement.

Top row S/S, X0, X1, X2, X3, NC. Bottom row NC, X4, X5, X6, X7, NC. All eight channels share one S/S terminal. To use both PNP and NPN outputs in that group, match them to a common input arrangement using a suitable signal converter or interposing relay. Leave the unused NC terminals unconnected.

PLC addressing, software and cable

X0–X7 are the local terminal labels. For example, when this is the first digital expansion after a DVP32ES200R, the CPU reads its eight inputs at X20–X27. Local X0 maps to X20 in the program. Check the starting address against the CPU model, preceding modules and hardware configuration. Use the actual CPU X address in the ladder diagram and on the HMI diagnostics screen.

Load the program into the host CPU. For DVP-ES2 and DVP-EX2, use WPLSoft or ISPSoft as supported by that CPU. Set up the ISPSoft connection in COMMGR. For COM1 RS-232 on a standard ES2/EX2 CPU, use UC-PRG020-12A from USB or UC-MS020-01A from a PC with an RS-232 port. Install the appropriate USB cable driver and select the correct COM port.

Delta’s CPU manual lists DIADesigner or ISPSoft for standard ES3 CPUs and DIADesigner for ES300TEC and EX3. Use the USB data cable or RJ45 Ethernet connection that matches the host CPU port. Select the PLC cable by CPU model.

Related models and topics

DVP16XM211N provides 16 digital inputs. DVP08XP211R has four inputs and four relay outputs. DVP08XP211T has four inputs and four transistor outputs. DVP08XM11N is the eight-input model for the earlier ES/EX generation. When replacing PLCs and modules, compare exact part numbers and host compatibility.

When troubleshooting, first measure the power supply voltage with the sensor operating. Route sensor wiring away from drives and motor cables to reduce electromagnetic interference. When laying out panel components, show protective grounding and 0 V distribution as separate items on the wiring diagram.

Editor’s Note

When buying a used module, get clear photographs of the label and the side expansion connector. The 211 portion of 08XM211N identifies the correct family.

If all eight inputs disappear together, start with S/S, the field supply and the side connector. One loose common connection can affect every working channel.

Use a known-good 24 V DC test signal on one channel. Verify the input LED first, then check the corresponding X address in the CPU’s online monitor.

If the LED changes and the monitored bit stays fixed, check the CPU model and expansion order. The X0 terminal could map to X20 in the program.

If an input remains ON after a sensor replacement, check the PNP/NPN type, S/S polarity and any leakage from a two-wire sensor. Record both ON and OFF for each of the eight channels during acceptance testing.

PDF manuals and technical documents

See the Delta DVP PLC files page for series documentation. In the DVP module manual, section 2.5.1 shows the terminal layout and 2.6.1.3 shows PNP/NPN wiring. Section 1.1 of the PLC/HMI cable guide shows the standard ES2/EX2 CPU connections.