Delta DVP16XM211N
Delta DVP16XM211N adds 16 digital 24 V DC inputs to a compatible PLC CPU in the DVP-ES2 / EX2 expansion family. Its configuration is 16 DI / 0 DO. The host PLC reads the states of pushbuttons, limit switches and sensors at X addresses.
Use inductive sensors for metal targets, capacitive sensors for suitable materials and photoelectric sensors to detect passing products. Compare the module’s 10–15 ms input response with the pulse duration. For fast encoder signals, choose a suitable high-speed CPU input or counter module.
Specifications and mounting
Input ratings. 24 V DC, 5 mA per channel and 4.7 kΩ input impedance. The ON threshold is >15 V DC and the OFF threshold is <5 V DC. Response is 10 ms ±10% from OFF to ON and 15 ms ±10% from ON to OFF. Each input has a status LED.
Power. The host CPU supplies the module electronics with 24 V DC through the expansion bus. The installation sheet lists 2.4 W consumption. Size the 24 V DC field circuit separately for the sensors. Check the available current if using the CPU’s auxiliary 24 V output. Select a suitable power supply, DIN rail 24 V DC supply and field-circuit fuse as needed.
Mounting. Removable terminal blocks, 35 mm DIN rail or M4 screws. The module is 70 mm wide, 78 mm deep and 90 mm high at the body. The Type 2 drawing shows an overall height of 110 mm and horizontal hole spacing of 62 mm. Weight is approximately 148 g. Operating temperature is 0–55 °C. Leave room for terminal removal and wire bends around adjacent panel components.
S/S and input terminals
The upper row carries S/S and X0–X7. The lower row carries S/S and X10–X17. Leave the NC terminals unconnected. Delta’s section 2.5.6 shows both S/S terminals at the same reference. For PNP sensors, connect both S/S terminals to 0 V. For NPN sensors, connect both to +24 V. Check the field wiring and common references before changing the sink/source arrangement.
A volt-free auxiliary contact from an interface relay or contactor can also signal into the 24 V DC input circuit. Use the relay contact to switch the field circuit’s 24 V DC signal. Keep mains voltage away from X and S/S terminals.
CPU addresses, software and programming cable
On a DVP32ES200R/T with 16 built-in inputs, X0–X17 belong to the CPU. With DVP16XM211N as the first digital input expansion, local X0–X7 become X20–X27 in the program. Local X10–X17 become X30–X37. Addressing is octal. If the CPU or expansion order changes, verify the starting address in online monitoring.
Program the DVP-ES2 or DVP-EX2 host using WPLSoft or a CPU-compatible version of ISPSoft. Check COMMGR settings for an ISPSoft connection. Read the module’s X bits in the host PLC program. The CPU makes the input states available to the automation sequence, HMI and SCADA application.
Connect the programming cable to the host CPU. Delta lists UC-PRG020-12A for a suitable 8-pin mini-DIN RS-232 COM1 port. The cable is 2 m long with a DB9 female PC connector and a male mini-DIN PLC connector. For a PC without a serial port, check the driver and COM number of a suitable USB–RS-232 adapter.
Related models and topics
DVP08XM211N provides 8 digital inputs. DVP16XM11N is the 16-input model from the earlier ES/EX generation. Compare the host family and expansion connector before replacing a unit. DVP16XP211R and DVP16XP211T provide 8 inputs plus 8 relay or transistor outputs respectively.
If you need outputs alongside 16 inputs, compare the channel count, supply and output type of DVP24XP200R, DVP24XP200T, DVP32XP200R and DVP32XP200T. For output-only expansion, see DVP08XN211R, DVP08XN211T, DVP24XN200R and DVP24XN200T.
Editor’s Note
Start with the complete label. 16XM211N and the earlier 16XM11N look close on paper. Check the host CPU and expansion connector before choosing a replacement.
If an entire row is silent, check its S/S wiring and removable terminal block first. For a single suspect channel, compare it with a working input using the same test contact.
If the input LED changes while the program bit stays fixed, monitor the actual CPU X address. Check the octal sequence as you move from the upper row to the lower row.
Isolate power before removing the module. Inspect the bus connector for bent pins and terminal solder joints for cracks. If a whole group behaves differently, trace its common connection.
When buying a used unit, request photos of both terminal blocks. Bench-test all 16 inputs in both states with a compatible CPU, checking the LEDs and the online X bits.
PDF manuals and technical documents
Use these two documents via the Delta DVP PLC files page. In installation sheet DVP-0131130-01 dated 21 February 2024, PDF pages 3–4 cover power and input ratings and page 9 shows terminal assignments. In module manual DVP-0399820-05 dated 6 January 2026, the wiring diagram is section 2.5.6, printed page 2-12, PDF page 46.
DVP16XM211N main page · ES2/EX2 modules · DVP expansion modules · DVP PLC series · Delta PLC · Used Delta models · Delta manuals
External references
Delta DVP-ES2 DIDO installation instructions · Delta DVP Series Module Manual · Delta DVP/TP catalogue