Delta DVP24XN200T
Delta DVP24XN200T – 24 NPN Transistor Output Expansion Module
Delta DVP24XN200T is a DVP expansion module with a 100–240 V AC supply and 24 digital outputs. The outputs are NPN sinking transistors; there are no digital inputs. It requires a host PLC CPU and follows the main PLC program.
Delta's selection catalogue lists this module with the DVP-ES2, DVP-EX2 and DVP-ES3 digital expansion families. Do not substitute an older XN11T/XN00T unit or another DVP housing by appearance alone. Check the complete model, expansion interface, CPU limits and terminal arrangement.
Supply and output ratings
The L/N operating supply is 100–240 V AC, while the switched output circuit is rated for 5–30 V DC. These are separate circuits. A transistor output is not a dry contact and cannot directly switch an AC load. Use a suitable interposing relay or a correctly specified, DC-controlled SSR where required.
The manual contains conflicting current ratings: the selection table in the 6 January 2026 DVP Module Manual states 0.5 A/output and 4 A/common; its detailed electrical table and exact DVP24XN200T wiring section state 0.3 A/output and 1.2 A/common. This page uses the lower detailed ratings for load calculations. Obtain manufacturer clarification for the exact hardware before relying on the higher figures.
The detailed table specifies 100 Hz maximum resistive-load switching, 50 µs OFF-to-ON and 200 µs ON-to-OFF. CPU scanning and application logic also affect operation. These ratings do not make this a dedicated high-speed pulse output or servo positioning module.
UP/ZP supplies and output groups
The wiring instructions require an external 24 V DC supply (−15% / +20%) for UP0–UP3 and ZP0–ZP3. Connect UP to +24 V and ZP to 0 V. In the NPN circuit, the load connects between the positive supply and its Y output. Applying the AC operating supply does not remove this external DC supply requirement.
UP0/ZP0: Y0–Y7; UP1/ZP1: Y10–Y17; UP2/ZP2: Y20–Y23; UP3/ZP3: Y24–Y27. The terminal numbering is octal: Y0–Y27 represents 24 outputs. Check the total current of each common group. Eight outputs at 0.3 A each would draw 2.4 A, exceeding the detailed 1.2 A group limit.
The wiring note's 30 mA figure concerns auxiliary driver consumption, not the total permitted load current. Do not treat the separate +24V/24G terminals as this AC module's main supply input or parallel an external supply into them without checking the circuit. Leave NC terminals unused. Include protective earth, grounding, fuses and correct fuse sizing in the installation review.
Addressing and commissioning
The Y labels identify local terminals. Actual program addresses depend on the host CPU's built-in outputs and preceding modules. Match the I/O module layout to the project's Y allocation. This module adds no physical X inputs. Secure the DIN rail mounting and expansion connection with power isolated, then begin testing with a low-current load.
Programming software and cables
DVP24XN200T has no separate user program. PLC programming takes place in the host CPU. For ES2/EX2, use WPLSoft or a CPU/version-compatible ISPSoft release. Standard ES3 uses ISPSoft or DIADesigner; WPLSoft is not supported. Confirm the exact CPU code and project version when selecting programming software.
ES2/EX2: the host CPU's COM1 RS-232, 8-pin mini-DIN port accepts the UC-PRG020-12A active USB-to-RS-232 programming cable. Install its USB serial driver and select the correct virtual COM port. UC-MS020-01A is an alternative for a real RS-232 port; a USB-only computer additionally needs a suitable converter.
ES3: use a data-capable cable for the CPU's Mini-B USB port, the manufacturer's USB driver and the software's communication settings. Do not confuse this with the serial mini-DIN connection. Programming cables connect to the CPU, not the output module; this module has no independent Modbus RS-485 port.
Related model differences
DVP24XN200R provides 24 relay outputs with a different contact/common arrangement. DVP08XN211T offers 8 NPN outputs and DVP16XN211T offers 16. DVP24XP200T instead has 16 inputs and 8 outputs. These are comparison models, not automatic wiring-compatible replacements.
Editor's Note
Start with the full 200T label and the L/N supply marking. A 24 V load circuit does not mean the module itself has a 24 V DC operating supply.
An illuminated LED does not prove an output works under load. Test each group with an appropriate low-current load and measure its Y terminal against the relevant ZP reference.
If a complete group fails, check its UP/ZP supply, fuse and terminal connections first. Begin PLC troubleshooting with those measurements before condemning the transistor stage.
Check suppression on inductive loads. A correctly polarised diode may suit a DC coil, but consider the required release time when choosing the suppression method.
Back up the CPU program and address list before replacement. Remove forced outputs before returning the machine to automatic operation, and verify the replacement's terminal layout.
This is a standard output module. Emergency stops and hardware interlocks require their own appropriate design as part of PLC system safety.
PDF manuals and related topics
Start with the Delta DVP PLC files page. For this model, consult Chapter 2 of the DVP Module Manual, especially printed page 2-18. The selection catalogue and CPU cable guide are supplementary references. All three archived documents are in English.
Related topics: analogue versus digital signals, how optocouplers work and PLC programming languages.
Navigation: Delta main page · Delta PLC · DVP series · ES2/EX2 modules · DVP PDF archive.
External references
Delta DVP Series Module Manual, 6 January 2026 (manufacturer document, distributor archive) · DVP selection catalogue, 3 January 2023 · PLC/HMI Cable Selection Guide, 15 August 2019.
ES3 family programming manual, 6 March 2024 · ES3 family hardware manual, 12 December 2023. Delta's access terms may apply to official downloads.