Delta DVP10SX11R
Delta DVP10SX11R — 4 digital inputs, 2 relay outputs, 2 AI and 2 AO
The Delta DVP10SX11R is a 24 V DC PLC CPU from the original DVP-SX series. It has 4 digital inputs, 2 relay outputs, 2 analog inputs and 2 analog outputs. The analog circuits have 12-bit resolution. The two-digit front display can show the PLC station address, a user value or an error code.
In a pump application, an analog input can read a pressure transmitter. The PLC scales the pressure and can use PID to calculate a speed reference for the drive’s analog input. Match the analog signal type at both devices. 0–10 V and 4–20 mA use different wiring and scaling.
Supply, digital I/O and relay terminals
The CPU uses a 20.4–28.8 V DC supply and consumes 5 W according to the installation sheet. X0–X3 share the S/S input common. Connect S/S to +24 V for an NPN sensor or 0 V for a PNP sensor. Y0/C0 and Y1/C1 are separate relay contacts. Feed each load circuit through its matching common. Check the 1.5 A per output limit against load type and inrush current.
Analog wiring and D registers
For voltage input, use the channel’s V+ and COM. For current input, jumper V+ to I+ on the same channel as shown in Delta’s diagram, and return the current loop through COM. For analog voltage output, use V+/COM. For current output, use I+/COM. Route analog input and output wiring away from motor and drive power cables.
D1056/D1057 hold the present analog readings for CH0 and CH1. D1110/D1111 hold their averages. D1116/D1117 hold the analog output commands. Delta scales +10 V to +2000. At +20 mA, the raw value is +1000 for input and +2000 for output. A 4–20 mA input therefore spans nominal counts of 200–1000. With a 0–10 bar transmitter, 12 mA → about 600 counts → 5 bar.
Programming software, cable and communication
Use WPLSoft or an ISPSoft version supporting the SX CPU for PLC programming. Select the DVP-SX CPU family. Delta’s programming manual specifies 7,920 steps for SX and 15,872 steps for SX V3.0 and later. Check the CPU version before transferring an existing project.
Delta’s cable guide lists the UC-PRG020-12A USB programming cable for COM1 RS-232. The UC-MS010-02A and other DVP programming cables are options for a suitable serial connection. In ISPSoft, select the correct COM port through COMMGR. COM2 RS-485 can connect to Modbus RTU devices. Delta shows the IFD6500 converter for a PC connection over RS-485.
Editor’s Note
When buying used, check the R nameplate suffix and the C0/C1 terminals. Test each relay with a suitable load. Check both the front LED and whether the contact opens and closes.
If a current input reads low, check the V+/I+ jumper and continuity of the current loop first.
If the HMI value fluctuates, compare the D1056/D1057 present values with the D1110/D1111 averages. Check cable routing and analog COM.
Safely prevent drive motion during output testing. For a voltage output, set D1116 = 1000 and check for roughly 5 V across V+/COM with a multimeter.
Back up the program and any required retained data before removing the CPU. A front display code of Er01 indicates a program syntax error. Er02 indicates program loss.