Delta DVP20SX211T
Delta DVP20SX211T — SX2 PLC with 4 Analog Inputs and NPN Outputs
The Delta DVP20SX211T is a 24 V DC DVP-SX2 PLC CPU with 8 digital inputs, 6 NPN transistor outputs, 4 analog inputs and 2 analog outputs. It combines analog measurement and positioning in one CPU, with 16K steps of program memory and two 100 kHz pulse outputs.
Digital I/O and supply
X0–X7 accept 24 V DC signals. Wire the S/S common for the NPN or PNP sensors used in the panel. Y0–Y5 are NPN sinking outputs. Delta specifies 0.5 A per point and 3 A per ZP for resistive loads. Connect an external 24 V DC supply to UP and ZP as shown in Delta’s wiring diagram. The unit mounts on a 35 mm DIN rail inside the panel.
Pulse outputs. Y0 and Y2 are rated up to 100 kHz, Y1 and Y3 up to 10 kHz, and Y4 and Y5 up to 1 kHz. For stepper motor control using pulse and direction signals, check the drive’s input voltage, signal polarity and pulse frequency.
Built-in analog channels and registers
4 AI, 12-bit. AD0–AD3 accept ±10 V, ±20 mA and 4–20 mA. Raw ranges are −2000 to +2000, −2000 to +2000 and 0 to 2000, respectively. Read channel values in D1110–D1113. Set the analog input to match the sensor’s analog signal range. For current input, bridge the channel’s V+ and I+ terminals as shown in Delta’s wiring diagram.
2 AO, 12-bit. DA0 and DA1 use −2000 to +2000 for ±10 V, and 0 to 4000 for either 0–20 mA or 4–20 mA. Write output values to D1116 and D1117. The allowable load is up to 500 Ω for current output and at least 5 kΩ for voltage output. D1115 sets the voltage or current mode and current range for each channel. D1062 sets input averaging. For analog signal applications, check the physical wiring, D1115 settings and scaling in that order.
Programming software and cables
Select DVP-SX2 in WPLSoft or ISPSoft to create a ladder program. For the Mini‑USB Type‑B port, use UC-PRG015-01A or UC-PRG030-01A. Install the SX2 USB driver and select the COM port shown in Windows. With ISPSoft, create an RS-232 driver in COMMGR and match the communication settings to the CPU.
For COM1 RS-232, use UC-PRG020-12A with a USB-equipped PC or UC-MS020-01A with a PC serial port. COM2 provides RS-485. When using Modbus RTU with an HMI or drive, match the station address, baud rate and frame settings. See Delta PLC cables, PLC programming and industrial communication for more on port selection.
Field application
In a pump panel, connect a 0–10 bar pressure transmitter to AD0 and send the drive speed reference from DA0. To select 4–20 mA for AD0, set bits 0 and 8 of D1115. In this mode, 12 mA corresponds to about 1000 counts and 5 bar. Use this value as feedback and scale the drive reference using DA0’s range. See PID control and PID control with a PLC for the control loop.
Editor’s Note
When buying used, check the T suffix on the label, the power connector and the analog terminals. The R suffix indicates relay outputs and the S suffix indicates PNP transistor outputs.
If a Y LED lights and the load stays off, use a multimeter to check the UP–ZP supply, the load’s +24 V connection and the NPN current path.
Test the analog inputs at 4, 12 and 20 mA. Measure the analog outputs separately with a suitable test load. Check that D1115 matches the terminal wiring.
If readings fluctuate when the drive starts, route signal cables away from motor leads. Check shield connections, grounding and sources of electromagnetic interference.
When switching DC coils, verify output limits and coil suppression. Use a suitable interposing relay or contactor where the load requires it.
Back up the program and accessible retained data before replacing a CPU. Verify the inputs, analog scaling and outputs separately with the drives and motion outputs in a safe state.
Related models and pages
The DVP20SX211R has relay outputs and the DVP20SX211S has PNP outputs. The DVP10SX11T belongs to the earlier SX generation. The DVP20EX200T is an EX2 option with a different housing and supply. See Derell PLCs and smart relays for other applications.
Delta DVP-SX2 · Delta DVP PLC series · Used Delta PLCs · Delta Automation
Manuals and wiring diagrams
Delta DVP PLC files · ISPSoft user manual
External references · SX2 installation and wiring sheet, 2024 · English and Turkish instruction sheet, 2014 · DVP programming manual, analog registers · SX2 programming cable diagram