Delta DVP20SX211R

Delta DVP20SX211R – SX2 analog PLC with relay outputs

The Delta DVP20SX211R is a compact 16K-step PLC CPU in the Delta DVP-SX2 series. It has eight digital inputs, six relay outputs, four analog inputs and two analog outputs. Its nominal supply is 24 V DC, with an operating range of 20.4–28.8 V DC. The same CPU can read a tank level signal, issue a pump command through a relay output and send an analog reference to a drive.

Digital inputs and relay outputs

X0–X7 are 24 V DC sink/source digital inputs with an S/S common. Y0–Y2 share C0 and Y3–Y5 share C1. Delta rates the relay contacts at 1.5 A per output and 5 A per common for resistive loads. See the manual for inductive load limits and contact protection. For high-speed pulse outputs, choose a suitable transistor model. The DVP20SX211T has NPN outputs and the DVP20SX211S has PNP outputs.

Built-in analog I/O and D registers

The 12-bit analog I/O supports ±10 V, ±20 mA or 4–20 mA on the inputs and ±10 V, 0–20 mA or 4–20 mA on the outputs. Use VO–AG for voltage output and IO–AG for current output. For current input, jumper the channel’s V+ and I+ terminals as shown in Delta’s wiring diagram. Check that the field wiring matches the selected mode.

In the ladder program, D1110–D1113 hold the four averaged input readings and D1116 and D1117 hold the two output commands. D1115 selects channel modes, D1114 enables or disables inputs, and D1062 sets the averaging count. In 4–20 mA mode the input scale is 0–2000 and the output scale is 0–4000. A 12 mA input reads approximately 1000. An output command of 2000 produces approximately 12 mA.

Programming software, Mini USB and serial ports

Program the CPU in WPLSoft or ISPSoft. Select DVP-SX2 as the new project target. The built-in Mini USB Type-B port accepts the UC-PRG015-01A or UC-PRG030-01A data cable. Install the appropriate Windows USB driver and select the assigned COM port. Delta’s ISPSoft manual specifies RS-232 as the COMMGR driver type for the SX2’s built-in USB-to-serial converter.

For COM1 RS-232, use the UC-PRG020-12A with a USB port at the PC or the UC-MS020-01A with a PC serial port. COM2 supports RS-485 Modbus communication. Select right-side expansion modules from the CPU compatibility table. An Ethernet installation that supports left-side expansion can use a separate communication module such as the DVPEN01-SL.

Editor's Note

When buying used, check for DVP20SX211R on the label and C0/C1 on the terminals. Inspect the Mini USB port and expansion connectors.

On the bench, measure the 24 V DC supply first. Back up the machine program and D1115 settings before downloading a new project.

Test the relay outputs individually with a suitable low-voltage test load. If the output LED lights and the load stays off, check the common supply and relay contacts.

Test the analog channels individually. If readings drift when a motor starts, check cable routing, electromagnetic interference and grounding.

When checking an output with a multimeter, account for the receiving device’s load. Delta specifies at least 5 kΩ for voltage output and up to 500 Ω for current output.