Delta UC-PRG030-01A
Delta UC-PRG030-01A — 3 m USB-to-Mini USB PLC Programming Cable
Delta UC-PRG030-01A is a 3 m programming and data cable connecting a computer USB port to the mini USB Type-B port of a compatible PLC. It belongs to the Delta DVP programming cable range and provides a connection for project transfer and online monitoring on suitable DVP and AS PLC devices.
This model carries USB data. It does not replace an external USB-to-RS-232 or USB-to-RS-485 converter. Check the PLC’s physical port, its computer-side device driver and software support for the target model together.
Connectors and pin connections
Computer end: USB Type-A. PLC end: mini USB Type-B. Length: 3 m. Delta’s Figure 10 shows the +5V, D−, D+ and GND connections below. Data conductors are required; a power-only cable cannot establish a programming connection.
| Signal | PLC-side mini USB | PC-side USB |
|---|---|---|
| +5V / VBUS | 1 | 1 |
| D− | 2 | 2 |
| D+ | 3 | 3 |
| GND | 5 | 4 |
The +5V line belongs to the USB connection. Supply the PLC’s normal operating power according to its own manual; connecting USB does not establish that all PLC functions are powered. Mini USB and micro USB are also different connector types.
Documented device examples
The DVP-SX2 connection diagram includes UC-PRG030-01A. Example CPUs are DVP20SX211R, DVP20SX211T and DVP20SX211S. This does not mean that every DVP CPU has the same USB port.
The AS hardware manual specifies UC-PRG030-01A as a 3 m mini USB programming cable for AS332T-A, AS332P-A and AS324MT-A in the AS300 range. Check the accessory table separately for other CPU generations.
USB driver and COMMGR settings
Even with a healthy cable, communication may fail until the PLC USB driver is recognised correctly. When using ISPSoft and COMMGR, check the device detected by Windows and its assigned port. Select WPLSoft according to support for the specific DVP model.
Delta’s ISPSoft manual distinguishes the interfaces: DVP-SX2 performs USB-to-RS-232 conversion inside the PLC and uses the RS-232 connection type in COMMGR. AS USB connections use USB (Virtual COM). Do not automatically apply identical communication settings to CPUs with similar-looking connectors; follow the method documented for the target model.
Differences from related cables
UC-PRG015-01A is the 1.5 m option for the same mini USB connection type. UC-PRG030-02A and UC-PRG015-02A are separate USB Type-B models. Cable length alone is insufficient when selecting between the 01A and 02A suffixes.
UC-PRG030-10A is a female DB9-to-female DB9 RS-232 cable; UC-PRG030-20A has RJ45 connectors. UC-PRG020-12A is a different USB serial connection arrangement. Compare the port standard and connector type together when selecting DVP communication cables.
Editor’s Note
If the computer cannot detect the PLC at all, first try a short, known-good data cable. Not every mini USB cable in a drawer carries data; a power-only cable can send you looking for software faults that are not there.
Pressing a cable into a loose mini USB socket is not a lasting repair. With power isolated, inspect the socket terminals and solder joints. Heavy cables or adapters can put the same strain back on the repaired connector.
Check the detected device and any warning symbol in Device Manager. Separate driver problems from cable faults before repeatedly reinstalling software. Trying another computer USB port can also help isolate the cause.
If transfers stop partway through, inspect the connector entries and crushed cable sections. Try a direct computer connection first, then check any extension cable or USB hub separately.
Record the existing project, CPU model and communication settings before downloading. Resetting a working PLC or loading arbitrary firmware is not an appropriate response to a connection fault.
Avoid bundling the cable tightly with motor and drive power wiring. Route a temporary maintenance connection where the cabinet door cannot crush it or apply sideways pressure to the mini USB socket.
PDF, software and related topics
Use the Delta PLC accessories PDF and software files page for cable diagrams and software links. CPU installation and driver information can also be checked through Delta PLC and HMI manuals.
Navigation: UC-PRG030-01A main page · Delta PLC accessories · Delta PLC models · Used Delta products
External references
Delta PLC/HMI Cable Selection Guide — Figure 10, 1-85 · Delta AS Hardware and Operation Manual — Programming Cable · Delta ISPSoft User Manual — USB / COMMGR · Delta DVP / TP Catalogue — Programming Cables