Delta DVP20SX211S

Delta DVP20SX211S – DVP-SX2 PLC with PNP Outputs

Delta DVP20SX211S is a compact Delta DVP-SX2 PLC with 8 digital inputs, 6 PNP transistor outputs, 4 analog inputs and 2 analog outputs. It stores up to 16k program steps. The built-in analog channels can read a pressure transmitter and send a speed reference to a variable-frequency drive under PID control.

Power supply, digital I/O and pulse outputs

The CPU runs on 24 V DC (20.4–28.8 V DC). X0–X7 are 24 V DC inputs. For three-wire PNP and NPN sensors, wire the S/S common to 0 V for PNP and +24 V for NPN.

Y0–Y5 are sourcing PNP outputs that supply positive voltage to the load when on. Delta specifies an external 5–30 V DC output supply at UP/ZP and resistive limits of 0.3 A per output and 1.8 A per UP common. High-speed pulse limits are 100 kHz on Y0 and Y2 and 10 kHz on Y1 and Y3. Check that the servo drive’s pulse input circuit supports the PNP output. When using an encoder, check the CPU’s high-speed counter table for the relevant input.

12-bit analog I/O and scaling

The four analog inputs support ±10 V, ±20 mA or 4–20 mA. The two analog outputs support ±10 V, 0–20 mA or 4–20 mA. Select each channel’s mode in D1115. Read inputs from D1110–D1113 and write output commands to D1116 and D1117. For a current input, bridge the channel’s V+ and I+ terminals as shown in Delta’s wiring diagram.

Use separate input and output scaling for 0–10 V and 4–20 mA signals. In 4–20 mA mode, the input returns 0–2000 and the output command uses 0–4000. For example, 12 mA reads as approximately 1000 on an input and is commanded by approximately 2000 on a current output. For analog outputs, the load must be no more than 500 Ω in current mode or at least 5 kΩ in voltage mode.

WPLSoft, ISPSoft and programming cables

Program the PLC with WPLSoft or ISPSoft. For Mini‑USB Type‑B, Delta lists the UC-PRG015-01A or UC-PRG030-01A data cable. Check that the Delta USB driver is installed. In ISPSoft, establish the connection through COMMGR. For COM1 RS‑232, use UC-PRG020-12A USB-to-RS‑232 or UC-MS020-01A with a PC serial port. COM2 supports RS‑485 Modbus communication with HMIs, drives and instruments.

Editor’s Note

Check the S suffix on the label when buying used. The T version has NPN transistor outputs and the R version has relay outputs. Check the output commons before transferring existing panel wiring.

Connect by Mini‑USB during inspection and save a copy of the program. Check the RUN/STOP switch, terminal blocks and expansion connectors.

Watch a digital input change in the online monitor. Test each output with a suitable DC load and confirm that the load responds when the LED turns on.

Test the analog channels with a known current or voltage and monitor D1110–D1113. Measure the analog output in the selected mode with an appropriate load.

If the analog reading shifts when a drive starts, check cable routing and grounding. Connect the analog cable shield as shown by Delta and look for electromagnetic interference.