Delta DVP10SX11T
Delta DVP10SX11T DVP-SX PLC – 4 DI, 2 NPN DO, 2 AI, 2 AO
The Delta DVP10SX11T is a compact DVP-SX PLC CPU powered by 24 V DC. It has four digital inputs, two NPN transistor outputs, two analog inputs and two analog outputs. The built-in analog I/O handles signals such as pressure feedback and drive-speed references on the same CPU.
Terminal wiring and analog registers
Digital inputs are X0–X3 and outputs are Y0–Y1. Wire the S/S common to suit the PNP or NPN sensor according to Delta’s diagram. The two NPN outputs share C0. Route inductive sensor wiring and analog signal cables separately from power wiring in the control panel. Follow the manufacturer’s grounding diagram.
The built-in 12-bit analog channels support −10 to +10 V or −20 to +20 mA. To read current on an A/D channel, link that channel’s V+ and I+ as shown in Delta’s diagram. For D/A, connect to the V+ or I+ output and analog COM for the selected signal.
D1056/D1057 hold present input values and D1110/D1111 hold averaged input values. D1116/D1117 set the output values. For example, writing 1000 to D1116 gives a nominal 5 V command on CH0 in a 0–10 V application. A 4–20 mA input gives an ideal raw range of about 200–1000. Measure both endpoints at commissioning to verify scaling.
Drives, PID and pulse applications
In a pump application, feed the average pressure sensor reading into the PLC’s PID loop and send the analog output to the drive’s speed-reference input. Verify pressure scaling and the drive’s voltage or current setting before PID tuning. An HMI can show the raw input, the value in engineering units and the output command during commissioning.
Y0 and Y1 can supply pulses for a stepper motor or position control. Delta’s 2020 programming manual lists 50 kHz on Y0 and 10 kHz on Y1 for PLSY. The English table in the 2023 instruction sheet lists 32 kHz for Y0. For high-speed applications, verify the limit on the specific CPU revision.
Programming software, cable and communications
Use WPLSoft or ISPSoft for PLC programming and select DVP-SX as the CPU family. Set up the ISPSoft connection in COMMGR. The UC-PRG020-12A cable (2 m) connects the PC to the COM1 RS‑232 programming port. Delta also shows a suitable USB-to-RS‑232 adapter with the UC-MS020-01A cable.
COM2 RS‑485 supports Modbus ASCII and Modbus RTU for industrial communications. Match station address, baud rate and parity when connecting a panel or SCADA system. The two-digit display can show a station address or user code. Delta defines Er01 as a syntax error and Er02 as program loss.
Related models
The DVP10SX11R has the same I/O count with relay outputs. The DVP20SX211T is an SX2 option with more I/O. Consider the DVP08SP11T for digital expansion. For a new panel design, see the Derell B Series PLCs. Check wiring, analog scaling and program compatibility before replacing a CPU.
Editor’s Note
When buying used, ask for a photo of the 11T label and the analog terminals.
Back up the existing program before making changes. Check the RUN and error indicators.
Test both analog inputs separately with a known source. For current inputs, check the corresponding V+–I+ link.
Before connecting a drive, verify the analog outputs with a meter and suitable load. Compare the 0 V and 5 V commands in voltage mode.
Test both transistor outputs separately with a suitable load. For pulse applications, check frequency with an oscilloscope.
PDFs and technical documents
Related document index Delta DVP PLC files. The DVP-SX instruction sheet includes wiring in English and Turkish. The DVP-PLC Application Manual covers analog registers on PDF page 126 and PLSY on page 326. Section 1.5 of the Delta PLC/HMI Cable Selection Guide covers the PC connection.
DVP10SX11T main page · DVP PLC series · DVP-ES · Delta PLC accessories · Delta external terminals · Delta PLC · Used Delta models · Delta PLC and HMI manuals
Delta AS PLC · Delta AH PLC · Delta AH external terminals · Delta TP panels and remote I/O
External references
Delta DVP-SX Instruction Sheet (2011, TR/EN) · Delta DVP-SX Instruction Sheet (2023) · Delta DVP-PLC Application Manual (2020) · Delta PLC/HMI Cable Selection Guide (2019)