Delta DVP function cards
Delta DVP Function Cards
Delta DVP function cards add serial communications, Ethernet, CANopen or analogue I/O to compatible PLC CPUs. Start with the full CPU ordering code and the function you need. A plug-in card and a DVP expansion module can perform similar functions through different connectors. Check the built-in PLC I/O, communications ports and card slot when planning the installation.
Card selection table · Software and commissioning · PDF files
Choose a card by function
| Card | Function | What to check |
|---|---|---|
| DVP-F232 | RS-232 serial communications | Changes the COM2 interface on EH2. Operates as COM3 on EH3. |
| DVP-F422 | RS-422 serial communications | COM2 on EH2 and COM3 on EH3. Check the peer device’s Tx/Rx terminals and pinout. |
| DVP-F485 | Additional RS-485 port | Adds COM3 on a compatible EH3 CPU. The built-in COM2 retains its function. |
| DVP-F2AD | Two analogue inputs | 0–10 V or 0–20 mA. Reads sensor signals. Check input terminals and program scaling. |
| DVP-F2DA | Two analogue outputs | 0–10 V or 0–20 mA. Sends a reference to a drive or controller. Check the receiving input and load impedance. |
| DVP-FEN01 | Ethernet and Modbus TCP | For EH3 CPUs with 32 or more I/O points listed by Delta. DCISoft can configure the IP settings. |
| DVP-FPMC | Ethernet and CANopen communications | For compatible DVP-PM motion controllers. Verify the CPU model and required communications mode. |
Keep existing serial links working
Start an industrial communications check at the other device. RS-232 uses single-ended signalling. RS-422 and RS-485 use differential signalling. On a DVP-EH2 CPU, fitting an F232 or F422 assigns COM2 to the card and disables the built-in RS-485 interface. On a DVP-EH3, these cards operate as COM3. For the original DVP-EH, consult the sheet for the specific CPU and card revisions.
DVP-F485 and DVP-F485S have separate ordering codes. Check the documented F485S application for EH2 and the documented F485 COM3 behaviour for EH3. For Modbus over RS-485, confirm the station address, baud rate, parity and RTU or ASCII mode. Use the card manual to verify the supported master or slave role.
Where FEN01 and FPMC fit
FEN01 adds Modbus TCP access to a compatible EH3 CPU. When taking over an HMI or SCADA link, save the IP address, subnet mask and register map. The DVPEN01-SL is a separate Ethernet module that mounts on the left expansion interface of supported CPUs.
FPMC provides Ethernet and CANopen communications for the DVP-PM family. On a controller such as the DVP20PM00M, identify the interface used by the servo motor drive. Check the node address and data mapping for CANopen. For axes that use a pulse command, check the CPU output and drive input specifications. Chapter 11 of the DVP-20PM manual covers the two FPMC communications modes.
Analogue signal direction and scaling
F2AD reads a signal. F2DA sends a reference. For example, use F2AD to read a pressure transmitter and F2DA to send a speed reference to a variable frequency drive. The documented analogue signal ranges are 0–10 V and 0–20 mA. For a 4–20 mA transmitter, scale the low end of the measurement to 4 mA in the program.
Delta’s instruction sheet lists F2AD instantaneous values at D1056/D1057 and averaged values at D1110/D1111. F2DA output commands use D1116/D1117. Confirm these addresses in the CPU and card documentation, then check the measured value and commanded output separately at the bench.
Software and commissioning
Use WPLSoft or ISPSoft for the host CPU project, according to the hardware and project version. Configure the ISPSoft connection in COMMGR where applicable. Use DCISoft for FEN01 network settings and PMSoft for the DVP-PM project. Before changing the PLC program, save the current Ladder project, port settings and special register values it relies on.
Editor’s Note
Ask for both labels when buying used. Get a clear photo of the full CPU code and another of the card code. A single letter matters on cards such as F485 and F485S.
Trace the port before disconnecting it. If an HMI or drive uses COM2 on an EH2, a card change can affect the working link.
Use a known signal at the bench. For an input, check the raw value and engineering units. For an output, compare the program command with the measured voltage or current.
Read data after checking the Ethernet link LED. The LED shows a physical link. Confirm that the application reaches the intended CPU and register.
Back up the project and isolate power. Disconnect the CPU and field supplies before removing the card. Check the slot, connector, shielding and protective grounding. Keep the machine loads disconnected for the initial test.
Internal references and PDF files
Delta DVP PLC PDF files · CPU, programming and connection documentation.
DVP expansion modules · Delta PLC software · DVP-512FM backup memory for EH3 · Used Delta equipment
External references
Delta EH function card instruction sheet · COM2 and COM3 behaviour, analogue signals and card installation.
Delta cable selection guide · EH3 serial connections and the FEN01 CPU compatibility list.
DVP-FEN01 Ethernet operation manual · DCISoft, IP configuration and Modbus TCP.
DVP-20PM programming manual · FPMC, CANopen, Ethernet and PMSoft in chapter 11.