Delta AH digital modules
Delta AH Digital Input and Output Modules
Delta AH digital modules let a Delta AH500 PLC read sensors, pushbuttons and auxiliary contacts or switch field loads. This category covers 16-, 32- and 64-point options. Start with the input or output function, then match the voltage, output type and connector to the field wiring.
Digital input modules
16 inputs: The AH16AM10N-5A accepts 24 V DC inputs, and the AH16AM30N-5A accepts AC inputs. For DC sensors, identify the NPN or PNP output type and wire the S/S common according to the module diagram.
32 and 64 DC inputs: The AH32AM10N-5A uses a removable terminal block, the AH32AM10N-5B uses DB37, and the AH32AM10N-5C uses a latch connector. For 64 inputs, see the AH64AM10N-5C.
Relay, transistor and triac outputs
16 outputs: The AH16AN01R-5A has relay outputs. The AH16AN01T-5A has NPN sinking outputs, and the AH16AN01P-5A has PNP sourcing outputs. The AH16AN01S-5A uses triac outputs for AC loads. Check the load voltage, current per output and total current limit per common group together.
32 NPN outputs: The AH32AN02T-5A uses a terminal block, the AH32AN02T-5B uses DB37, and the AH32AN02T-5C uses a latch connector. For 64 NPN outputs, see the AH64AN02T-5C.
32 PNP outputs: The AH32AN02P-5A uses a terminal block, the AH32AN02P-5B uses DB37, and the AH32AN02P-5C uses a latch connector. For 64 PNP outputs, see the AH64AN02P-5C.
Cables, terminal boards and ISPSoft addressing
For DB37 and latch-connector modules, check the cable and terminal board part numbers together. See Delta AH I/O cables and Delta AH external terminals for the available options.
In HWCONFIG in ISPSoft, verify the module model, slot and start address. For example, a 32-point input module starting at X0.0 occupies X0.0–X1.15. Output modules use the same grouping with Y addresses. Select the PC connection in COMMGR.
Editor’s note
When buying a used module, check the full model code and the 5A, 5B or 5C suffix on the label.
Confirm whether the removable terminal block, cable and terminal board are included.
Inspect the front terminals for discoloration, the socket for bent pins and the rear rack connector for damage.
On the bench, apply a suitable test signal to inputs or use a suitable test load for outputs. Compare the LED with the X/Y status in ISPSoft and your measurement.
If an entire group fails to respond, check its common, field supply and cable before replacing the module.
Manual, wiring diagrams and addressing
Digital I/O specifications · Model-specific wiring diagrams · ISPSoft X/Y addressing. All three links open the relevant sections of the same English AH500 manual.
Related topics
Delta AH expansion modules · Delta AH analog modules · Delta AH PLC series