Delta AH16AM30N-5A
Delta AH16AM30N-5A | 16-Channel 120/240 V AC Digital Input Module
The Delta AH16AM30N-5A is a 16-channel AC digital input module for the Delta AH500 system. It has a removable terminal block and individual channel LEDs. It brings the status of devices such as selector switches, limit switches and relay auxiliary contacts in AC control circuits into the PLC program.
Input voltage, current and response time
The Delta AH500 hardware manual specifies 4.5 mA per input at 120 V AC and 9 mA at 240 V AC. The input turns on above 79 V AC and turns off below 40 V AC. The specified hardware response is 15 ms for OFF→ON and 30 ms for ON→OFF. Consider these times together with the PLC scan time when reading short pulses.
The AC input terminal layout shows channels 0–15 and two COM terminals. Use the wiring diagram for this model to trace the COM path for the selected channel. For 24 V DC field signals, see the AH16AM10N-5A input module and the guide to NPN and PNP wiring.
ISPSoft and X addressing
HWCONFIG in ISPSoft assigns one 16-bit X address group to the module. For example, if the start address is X2.0, channels 0–15 are read at X2.0–X2.15. Check the actual start address in the rack project. See Delta PLC software for the engineering tools.
Manuals and PDF downloads
AH500 Hardware and Operation Manual — PDF · English · 2023-04-12 · 678 pages. See printed page 2-29 for ratings, 4-33 for terminal and COM wiring, and 5-13 for X addressing.
Delta AH Series Catalogue — PDF · English. See the digital input table to compare models in the series. Further documentation is available in the Delta AH PLC PDF library.
Editor's Note
When buying a used unit, check the full AH16AM30N-5A part number and the 120/240 V AC marking on the label.
With power isolated, inspect the removable terminal block latch, the COM terminals and any signs of overheating.
Label the terminal wires before removing the module. Record the rack slot and the X start address in HWCONFIG.
If several inputs drop out together, check the shared field supply and COM wiring before replacing the module.
If the channel LED changes and the program bit stays fixed, use online monitoring to check the X address and the hardware assignment.
Related topics
Among the AH digital modules, the 24 V DC input options include the AH32AM10N-5A with a removable terminal block, the AH32AM10N-5B with a DB37 connector and the AH32AM10N-5C with a MIL connector. The AH64AM10N-5C provides 64 input channels.
For the output side, the AH16AN01R-5A has relay outputs and the AH16AN01S-5A has triac outputs. See AH power supplies for rack power options.