Delta AH16AN01S-5A
Delta AH16AN01S-5A 16-Point AC Triac Output Module
The Delta AH16AN01S-5A is a digital output module that adds 16 triac outputs to a Delta AH500 PLC rack. Delta identifies the outputs as 120/240 V AC. Field wiring uses a removable terminal block. The module switches AC circuits within its rated load limits.
The S suffix identifies triac outputs. In the same series, the AH16AN01R-5A uses relay contacts, the AH16AN01T-5A uses NPN outputs, and the AH16AN01P-5A uses PNP outputs. Check the full ordering code and field supply type when replacing a module.
Output current and COM groups
Delta rates resistive loads at 0.5 A per output and 2 A per COM. The terminals form four groups of four outputs. COM0 serves outputs 0–3, COM1 serves 4–7, COM2 serves 8–11, and COM3 serves 12–15. Add up the current of loads that operate simultaneously within each group.
The specified maximum switching frequency for resistive loads is 10 Hz. Select a suitable external switching device for inductive loads. See AH power supplies when planning rack power.
ISPSoft and output addressing
Add the module to its physical slot in HWCONFIG in ISPSoft. The module occupies 16 Y bits in the PLC project. For example, a start address of Y4.0 gives a last output address of Y4.15. See AH expansion modules for rack layout and Delta PLC software for engineering tools.
Manual and wiring diagram
AH16AN01S-5A triac output wiring diagram · In the English AH500 manual, the load ratings are on PDF pages 66–67, the COM wiring diagram is on page 205, and addressing is on page 301. Browse the series documentation under Delta AH PLC PDF files.
Editor’s Note
When buying used, verify the AH16AN01S-5A nameplate and check that the removable terminal block is included.
With rack and field power isolated, inspect the terminals for discoloration, cracks and loose screws.
On the bench, check outputs in all four COM groups with a suitable resistive test load.
Watch the load switch on and off while checking the output LED.
If four channels fail together, check that group’s COM connection and field supply before replacing the module.
Related topics
For input modules, see the AH16AM10N-5A, AH16AM30N-5A and AH32AM10N-5A. For 32-point DC output modules, see the AH32AN02T-5A NPN and AH32AN02P-5A PNP.
More from Delta · Delta PLC · Delta PLC accessories · Delta PLC and HMI manuals · Second-hand Delta products
External reference · Delta AH Series Catalogue