Delta AH32AM10N-5A
Delta AH32AM10N-5A 32-channel digital input module
The Delta AH32AM10N-5A provides 32 digital inputs at 24 V DC for the Delta AH500 PLC system. This AH digital module uses a removable screw terminal block. It brings signals from proximity sensors, limit switches, pushbuttons and auxiliary relay contacts into the PLC.
Electrical specifications and rack
Nominal input current is 5 mA per channel at 24 V DC, with 4.7 kΩ input impedance. Delta specifies an ON threshold above 15 V DC and an OFF threshold below 5 V DC. Response times are 10 ms from OFF to ON and 15 ms from ON to OFF, both with ±10% tolerance. The rated maximum input frequency is 50 Hz. For fast encoder pulses, consider the AH04HC-5A high-speed counter module.
Install the card in a compatible AH expansion slot. Check the rack power supply and the 24 V DC field sensor supply separately. If the panel uses an AHPS15-5A, verify the rack supply wiring against that unit’s connection diagram.
S/S wiring for PNP and NPN sensors
The 0 and 1 markings identify two input groups, each with channels numbered 0–15. For PNP sensors, connect that group’s S/S common to 0 V. For NPN sensors, connect it to +24 V DC. Apply the same wiring arrangement to channels that share an S/S common.
The 5A version takes field wiring at the removable terminal block. When selecting an AH external terminal or a Delta PLC accessory for a panel retrofit, match it to the exact module code and connector.
ISPSoft and input addressing
Use HWCONFIG in ISPSoft to match the card to its physical slot. For example, if the project assigns X2.0 as the start address in an AHBP03M2-5A main rack, the first group occupies X2.0–X2.15 and the second occupies X3.0–X3.15. Read the actual starting address from the existing project. See Delta PLC software for related tools.
Manual and PDF files
AH500 Hardware and Operation Manual — English PDF. See section 2.6.1 for electrical specifications, 4.7.11 for the terminal layout, 4.8.1.3 for PNP and NPN wiring examples and 5.4.1 for input addressing. Find related documents in the Delta AH PLC PDF archive.
Editor’s Note
When buying used, check the -5A suffix on the label and make sure the removable terminal block comes with the card.
Before removing the old card, photograph both terminal groups and label the S/S wires. The 0 and 1 groups are easy to swap during rewiring.
If an entire bank stays dark, check that group’s S/S common and sensor supply first. A loose common can affect every input in the group.
On the bench, test one input in each group. Confirm that the front LED and the X bit in ISPSoft change together. If the LED lights but the expected bit stays off, recheck the slot and start address.
The rated input voltage is 24 V DC. The 240 V DC entry at the top of section 4.7.11 is a printing error. The module label in the same drawing and the electrical specifications table both show 24 V DC.
Related topics
In the same 32-input family, the AH32AM10N-5B uses a DB37 connector and the AH32AM10N-5C uses a latching MIL connector. For other channel counts, see the AH16AM10N-5A and AH64AM10N-5C input cards. For output slots, see the AH32AN02T-5A NPN output and AH32AN02P-5A PNP output cards.
Delta AH PLC series · Delta PLC · Second-hand Delta equipment
External references
Delta AH500 Hardware and Operation Manual · Delta AH Motion Hardware Manual