Delta UN-03PF-01A is a 90° male DB9 connector for connecting PROFIBUS DP field cable to a device's communication port. It belongs to the Delta network connectors and Delta PLC accessories range. It provides the physical bus connection and switchable termination; the connected communication module performs the network's master or slave function.
The 01A version has no additional programming socket. Cable exit direction and maintenance access are relevant selection criteria. The manufacturer's catalogue drawing specifies H × W × D: 67 × 35.6 × 15.8 mm; allow additional space for cable bending and access to the connector screws.
PROFIBUS cable and DB9 pin assignments
Delta's connection example uses UC-PF01Z-01A PROFIBUS cable. Select the appropriate protocol-specific cable under Delta industrial network cables. Assess the shield connection, conductor ends and cable restraint together.
On the PROFIBUS DB9 interface, pin 3 is RxD/TxD-P, B (+) and pin 8 is RxD/TxD-N, A (−). Pin 5 is the DGND data reference and pin 6 is the VP positive-voltage connection. Check pin numbers together with the connector viewing direction; the apparent order reverses when viewed from the opposite side.
Using the termination switch
According to Delta's cable guide, set termination ON at the two physical ends of the PROFIBUS line and OFF at intermediate connectors. Identify an endpoint from the physical cable arrangement, rather than its station address or master role.
When replacing a station connector, record cable directions and switch position. A connection fault may affect more than the device being serviced; monitor the other stations on the line as well.
Use with Delta equipment
The manufacturer's PROFIBUS examples include the AH10PFBM-5A master, AH10PFBS-5A slave and AHRTU-PFBS-5A remote I/O unit. On the DVP side, DVPPF01-S also appears in the cable guide's applicable-device table.
Use AH communication modules and DVP special communication modules to investigate the associated ports and models. Mechanical fit alone does not establish protocol compatibility; verify the device's PROFIBUS interface and pin assignment.
Differences within the UN-03PF range
UN-03PF-02A combines a 90° connector with an additional female DB9 programming socket. UN-03PF-03A has a 180° connector arrangement and no additional programming socket. Consider cable exit direction together with the need for a service connection.
UN-03EN-04A is an RJ45 connection accessory serving a different interface from the PROFIBUS DB9 connection. Preserve the complete UN-03PF or UN-03EN code when ordering.
Editor's Note
For intermittent communication faults, inspect the physical connection before changing the PLC program. Loose DB9 screws, poor shield contact or incorrect termination can produce similar symptoms.
Do not wire solely by green and red conductor colours. Compare the cable's A/B markings with the device pin assignments; an earlier splice or repair may have changed the colour arrangement.
On a used connector, inspect bent pins, corrosion, a cracked cover and the cable-clamping area. Investigate a termination switch that will not hold its position or feels mechanically intermittent.
A single loose shield strand can touch a data terminal. Before closing the cover, inspect exposed conductors, shield contact and cable restraint; avoid transferring cable strain to the terminals.
Perform continuity and short-circuit checks with power isolated and the connection separated from devices. One resistance reading is insufficient to establish connector condition; switch position and connected circuit components can affect the result.
Photograph cable entry/exit directions and the ON/OFF setting before replacement. Put the process into a safe state before intervention, then check communication with the other segment devices as well as the serviced station.
PDF documents, software and related topics
Visit Delta PLC accessories PDF and software files for connection documents. Further manufacturer documentation is available under Delta PLC and HMI manuals. The connector does not require a separate program download; network settings belong to the relevant device configuration.
Related topics: Delta DVP PLC series + Delta AS PLC series + Delta AH PLC series.
Navigation: Delta products + Delta PLC models.
External references
Delta PLC/HMI Cable Selection Guide (4-8, 4-9 and 4-10); Delta AH catalogue archive (connector dimensions and accessory selection); Delta AH500 Hardware and Operation Manual (PROFIBUS port pin assignments).