Delta DVP64EH00T3

Delta DVP64EH00T3 – 64-Point PLC with Transistor Outputs

The Delta DVP64EH00T3 is a Delta DVP-EH3 PLC CPU powered by 100–240 V AC. It has 32 digital inputs rated at 24 V DC and 32 NPN open-collector transistor outputs. It provides 30,000 program steps and 12,000 words of data registers. In machine automation applications such as packaging, labeling and cutting, it can control both station sequencing and axis motion.

Inputs, outputs and addressing

Onboard addresses run from X0 to X37 and Y0 to Y37. The addresses use octal numbering. Direct digital expansion begins at X40 and Y40. When wiring an inductive sensor, photoelectric sensor or limit switch, check the signal level and the S/S input common against the diagram. PNP or NPN sensor wiring determines the input connection, while the NPN output type determines how the load is wired. For continuous measurements, compare analog and digital inputs and check the DVP04AD-H3 analog module if needed.

200 kHz counters and four-axis pulse output

Four high-speed counter channels can run at up to 200 kHz. The manual identifies the input groups as X0/X1, X4/X5, X10/X11 and X14/X15. When choosing an incremental encoder, check the A/B signal type and counting mode together. For a differential line-driver encoder, use the wiring diagrams to check signal compatibility and whether an interface is needed.

This T3 version supports pulse output up to 200 kHz on four axes through dedicated high-speed outputs. For position control, match the PLC pulse format, the drive input level and the common wiring. The PLC signal goes to the pulse input of a servo or stepper motor drive. For a drive such as the Delta ASDA-B2, consult the drive’s pulse input diagram. If counting is erratic, check protective grounding and possible sources of electromagnetic interference.

WPLSoft, ISPSoft and programming cable

Use WPLSoft or ISPSoft for PLC programming. Set the project target to DVP-EH3. Connect and back up the existing ladder program before making changes. For ISPSoft, configure the serial connection profile in COMMGR.

For COM1 (RS-232), use UC-PRG020-12A with a USB-equipped PC or UC-MS030-01A with a PC that has a physical RS-232 port. Install the USB cable driver and select the COM number shown in Windows. See Delta PLC cables for other connection options.

COM2 (RS-485) can be used for industrial communication. On an existing RS-485 Modbus link, record the station number, baud rate, parity and protocol mode. For a Modbus RTU connection to SCADA, verify communication after a CPU swap by reading a few known addresses.

Editor’s Note

Ask for a close-up of the label. When buying used, check the DVP64EH00T3 code and serial number. The R3 has the same I/O count and uses different relay output wiring.

Back up the machine first. With the machine in a safe state, save the PLC project, axis settings and order of the installed expansion modules.

Check beyond the LEDs. On the bench, test a standard output with a suitable load and verify the high-speed pulse channel you plan to use with an appropriate instrument.

Turn the encoder slowly. During testing, verify that the count changes correctly in both directions. If the count is reversed, check signal order and the program settings.

Control the first move. Under safe commissioning conditions, check direction, homing and limit response at low speed.