Delta DVP04AD-H3
Delta DVP04AD-H3 – 4-Channel Analog Input Module
Delta DVP04AD-H3 is a four-channel voltage/current input module for DVP-EH2/EH3 PLC systems. It converts field measurements into digital values for the host CPU. Within an analog I/O system it acquires measurements; consider DVP04DA-H3 for analog outputs. It is not a CPU running an independent user program.
An analog input represents a measured quantity rather than only an on/off state. The difference between analog and digital inputs matters here: this module is accessed through its control registers, rather than as ordinary X input contacts.
Input ranges, resolution and raw values
Select each channel independently: Mode 0: −10…+10 V; Mode 1: −5…+5 V; Mode 2: 1–5 V; Mode 3: 4–20 mA; Mode 4: −20…+20 mA; Mode F: disabled. Analog voltage or analog current selection must match both wiring and register settings. In 0–10 V and 4–20 mA applications, check digital scaling as well as the electrical range.
The normal range is −32000…+32000 in bipolar modes and 0…32000 in 1–5 V and 4–20 mA modes. With the standard curve, 4/12/20 mA → 0/16000/32000; in ±10 V mode, 0/5/10 V → 0/16000/32000. For example, a 0–10 bar transmitter with a 4–20 mA output uses pressure = raw value × 10 / 32000, so 16000 represents 5 bar. Use arithmetic wide enough to avoid overflow.
Data uses signed 16-bit two’s-complement words. The specification lists voltage resolution as 16 bits, 312.5 µV/LSB and current resolution as 15 bits, 0.625 µA/LSB. These LSB figures refer to the basic ±10 V and ±20 mA ranges. Resolution and measurement accuracy are different specifications.
Sensor and terminal wiring
For a voltage analog signal, connect the channel’s Vn+ and VIn− terminals. For current input, follow the manufacturer’s diagram: bridge Vn+ to In+ and pass the current between that combined terminal and VIn−. The current input includes 250 Ω resistance; voltage input impedance exceeds 1 MΩ. Do not add another parallel 250 Ω resistor to measure current.
Among analog sensors, 4–20 mA sensors and 0–10 V sensors require different connections. With a two-wire transmitter, account for loop supply and the transmitter’s required operating voltage. In analog signal applications, changing a register cannot correct field wiring. Channels are not isolated from one another; the digital and analog circuit sections are isolated.
Supply, response and expansion
External supply is 24 V DC, 20.4–28.8 V DC; maximum consumption is 2.5 W; operating temperature is 0–55 °C. Size the power supply for the module and field devices together. The ±15 V / ±32 mA absolute input limits are not normal measuring ranges.
The sheet specifies a 1 ms response time. PLC scan, read frequency and averaging add to overall system response. The module connects to the right-side expansion bus. Special modules are numbered 0–7 by distance from the CPU, sharing a maximum of eight special modules. DVP04AD-H3 occupies no digital X/Y points.
Programming software and cable
Program the host PLC using WPLSoft or ISPSoft. In a ladder diagram, use TO for mode/settings and FROM for measurements and diagnostics. An extension-module wizard supported by the installed ISPSoft version can also assist configuration and monitoring.
Connect the computer to the host PLC’s programming port. For the DVP-EH2 COM1 RS-232, 8-pin mini-DIN port, DVPACAB230 is a suitable cable option. A computer without a serial port needs a USB-to-RS-232 adapter and its driver. For ISPSoft, select the correct COM port in COMMGR, set it to START and select that driver in ISPSoft. For EH3 or another CPU, match the cable to that host’s actual port.
CR registers and four 4–20 mA channels
CR#0 model ID is H6407. CR#1 uses four bits per channel: CH1 b0–b3, CH2 b4–b7, CH3 b8–b11 and CH4 b12–b15. All four channels in Mode 3 require H3333; Modes 0/1/2/3 respectively require H3210. The default mode register is H0000. Do not transfer DVP04AD-H2 mode codes or scaling directly into an H3 program.
For the first special module, TO K0 K1 H3333 K1 selects 4–20 mA on all four channels. This affects every channel; apply it as an initialization setting with correct current wiring and calibration. CR#2–#5 set averaging counts: 1–20, default 10. CR#6–#9 contain averaged CH1–CH4 values; CR#12–#15 contain instantaneous values.
FROM K0 K6 D100 K4 reads averages into D100–D103; FROM K0 K12 D110 K4 reads instantaneous values into D110–D113. Replace K0 with the actual special-module index. In the sheet, Current Value means the present measurement, not exclusively a current measurement in mA.
Diagnostics, calibration and process control
FROM K0 K30 D120 K1 reads error status. CR#30: b0 supply abnormality, b1 hardware/GPIO failure, b3 OFFSET/GAIN error and b4/b5/b6/b7 hardware input-range errors for CH1/CH2/CH3/CH4 respectively. Multiple bits can be active. CR#34 reports firmware.
CR#18–#21 adjust OFFSET; CR#24–#27 adjust GAIN; CR#33 includes factory-setting restoration. Back up existing values before changing calibration. In PLC-based PID control, the host performs the PID calculation while this module acquires feedback. Displaying raw values, engineering units and error status together on an HMI helps diagnosis.
RS-485 and technical files
Standalone RS-485 supports Modbus ASCII and RTU. The module’s own RS-485 interface cannot be used while it is connected to the CPU expansion bus. CR#31 sets station address and CR#32 communication settings; the default is 9600 bit/s, 7E1, ASCII. Do not assume normal TO/DTO writes survive power loss; initialize required settings in the PLC program.
Reduce electromagnetic interference by separating shielded signal wiring from motor and mains cables. Follow the manufacturer’s FG and grounding diagram. Use Delta DVP PLC files for wiring, CR descriptions and conversion curves. Some formula headings retain inconsistent mode numbers; use the H3 CR table together with the Mode 3 conversion curve.
Editor's Note
Check the full model and CR#0 ID first. An H2 fitted in place of an H3 may require different program settings. Compare mode codes, raw scaling and terminal bridges, and preserve a copy of the working program.
Test a used module on all four channels at low, middle and high inputs using a calibrator. With the standard 4–20 mA curve, expect 0 at 4 mA, 16000 at 12 mA and 32000 at 20 mA. A zero raw value alone does not prove failure.
Inspect and measure the current-input V+–I+ bridge. A loose terminal can cause intermittent readings. Measure voltage in parallel and current using an appropriate series connection; never connect an ammeter across the supply.
For one drifting channel, disconnect field wiring and retest with a known source. If all channels move together, inspect the 24 V supply, reference and shielding first. Increasing averaging cannot repair poor supply or grounding.
After repair, check zero, full scale, stability after warming and settings after a power cycle, as well as the middle point. Do not conceal faults with OFFSET/GAIN. Record the reference instrument and measured results.
Related topics and navigation
DVP04AD-H3 main page · DVP-H3 modules · DVP06XA-H3 · DVP expansion modules · DVP PLC series · DVP PLC files
External manufacturer documents
Delta DVP04AD-H3 Instruction Sheet, 2017 · Delta DVP-EH2 Instruction Sheet, 2014 · Delta TP04G-AL/AL2, DVPACAB230 cable diagrams · WPLSoft / ISPSoft FAQ