Delta DVP32ES311T

Delta DVP32ES311T 24 V DC PLC with NPN transistor outputs

The Delta DVP32ES311T is a 24 V DC PLC CPU in the DVP-ES3 series. It has 16 digital inputs, 16 NPN transistor outputs and a 64K-step program capacity. The specified supply range is 20.4–28.8 V DC. Removable terminal blocks simplify servicing the input and output connections in a panel.

Inputs, output groups and pulse control

X0–X17 are octal addresses. The S/S common allows sink or source wiring for the 24 V DC inputs. Check the NPN or PNP type when connecting an inductive sensor. Delta’s hardware manual lists a maximum input frequency of 200 kHz on X0–X7. For an encoder, also verify the selected high-speed counter mode and input assignment.

Y0–Y7 use UP0/ZP0. Y10–Y17 use UP1/ZP1. The NPN outputs are specified for 5–30 V DC load circuits. Use the wiring diagram for the external 24 V DC auxiliary supply to the UP/ZP groups. Maximum switching frequency is 200 kHz on Y0–Y7 and 1 kHz on Y10–Y17.

The four positioning axes use Y0/Y1, Y2/Y3, Y4/Y5 and Y6/Y7. Match the pulse frequency and pulse/direction format to a compatible servo drive or stepper motor drive. Check the home and limit switch assignments in the project parameters.

Programming software, cables and communication

Delta lists ISPSoft 3.08 or later and DIADesigner for this CPU. Supported PLC programming languages include ladder logic and Structured Text. Use a USB-A to USB Mini-B data cable to connect a PC. Install the Delta USB driver and select USB (Virtual COM) in COMMGR. Programming is also available over RJ45 Ethernet.

The CPU has one 10/100 Mbps Ethernet port, two RS-485 ports and CAN. COM1 and COM2 are RS-485 ports. Match the serial settings to the connected device when using Modbus RTU. The Ethernet port supports Modbus TCP and EtherNet/IP Adapter. The CAN interface supports CANopen. Review the EtherNet/IP and Modbus TCP requirements when designing the panel network.

Editor’s Note

When buying a used unit, read the 311T suffix on the label and verify the 24 V and 0 V supply markings. The 32ES300T uses different supply terminals.

If the program is accessible, back up the project and hardware parameters. Record the existing network settings as well.

If the output LED lights but the load stays off, check the supply to the relevant UP/ZP group and the output circuit with a multimeter.

Check the pulse signal using the drive monitor or suitable test equipment. Use a safe test setup and low speed for the first movement.

If the encoder count is unstable, check the input filter, cable shield and grounding. Look for electromagnetic interference where signal cables run close to motor power wiring.

PDF manuals

See Delta DVP PLC files for installation and terminal diagrams.

Related topics and models

The DVP32ES300T is the 100–240 V AC model with 16 NPN outputs. The DVP32ES300R offers the same digital point count with relay outputs. For more digital points, see the DVP48ES300T and DVP64ES300T.

DVP32ES311T · DVP-ES3 · Delta DVP PLC series · Delta PLC · Used Delta automation

External references

DVP-ES3 instruction sheet (includes Turkish) · Delta hardware and operation manual (EN) · Delta programming manual (EN)