Delta DVP48ES300T
Delta DVP48ES300T — ES3 PLC with 24 Inputs and 24 NPN Outputs
The Delta DVP48ES300T is a 100–240 V AC DVP-ES3 PLC CPU with 24 digital inputs and 24 NPN transistor outputs. Its 64K-step program capacity, high-speed counting and pulse outputs suit conveyor, packaging and positioning applications.
Power, inputs and output groups
The CPU takes mains power at L–N and mounts on a 35 mm DIN rail. The built-in +24V/24G auxiliary supply provides up to 500 mA. For the 24 V DC digital inputs, S/S0 is the common for X0–X17 and S/S1 is the common for X20–X27. Wire each group to suit its NPN or PNP sensors.
UP0/ZP0 serves Y0–Y7, UP1/ZP1 serves Y10–Y17, and UP2/ZP2 serves Y20–Y27. Provide an external 24 V DC auxiliary supply to the groups in use, as shown in Delta’s diagram. The NPN outputs sink current toward 0 V. Delta rates resistive loads at 5–30 V DC, 0.5 A per output and 4 A per common. For coil loads, check coil current and suppression requirements when selecting an interposing relay or contactor.
High-speed inputs and positioning
Delta lists maximum input frequencies of 200 kHz for X0–X7, 10 kHz for X10–X17 and 50 Hz for X20–X27. For example, an inductive sensor can detect parts while an incremental encoder uses a high-speed input pair. The effective A/B count rate depends on the selected counter mode and input assignment.
Y0–Y7 are specified for switching up to 200 kHz and Y10–Y27 up to 1 kHz. For pulse and direction control of a stepper motor or servo motor, verify the output assignment and match the NPN interface to the drive’s input circuit.
Communications and memory
The RJ45 10/100 Mbit/s Ethernet port supports Modbus TCP and EtherNet/IP Adapter. See EtherNet/IP and Modbus TCP when choosing a protocol for a panel or supervisory system. COM1 and COM2 are RS-485 ports. A field drive can use Modbus RTU, for example. The built-in CAN port supports CANopen DS301. The microSD slot supports cards up to 32 GB. See industrial communication for more on field network wiring.
Programming software and cables
Program the standard DVP48ES300T with ISPSoft or DIADesigner. Delta’s manual lists ISPSoft 3.08 as the first release supporting ES3. Match the software version to the CPU firmware and the instructions used. Select the full CPU model when creating your ladder program.
USB connection. Use a data cable with Mini‑B at the CPU end. A USB‑A to Mini‑B cable works with a USB‑A PC port. Install the Delta USB driver and select USB (Virtual COM) and the Windows COM port in COMMGR.
Ethernet connection. Use an RJ45 Ethernet cable, put the PC and PLC on the same subnet and select the PLC IP address. See PLC programming and Delta PLC cables for connection options.
Editor’s Note
When buying used, check for the exact DVP48ES300T label and make sure all removable terminal blocks are included. The R-suffix CPU uses different output wiring.
If a Y LED lights and the load stays off, use a multimeter to check the relevant UP/ZP group and the load supply. Test all three output groups separately.
For encoders or pulse outputs, use X0–X7 and Y0–Y7 according to the channel assignments in the manual. Keep general-purpose points within their own speed ratings.
If the PLC does not appear over USB, check the data cable and driver first. On Ethernet, check the IP address, subnet mask and any duplicate address.
If counts become erratic when a drive starts, route signal wiring away from motor leads. Check cable shields, grounding and sources of electromagnetic interference.
Before changing the CPU, back up the program, accessible retained data and communication settings. On the first test, verify sensor and output assignments with motion outputs disabled.
Related models and pages
The DVP48ES300R has 24 digital inputs and 24 relay outputs. The DVP32ES300T, DVP64ES300T and DVP80ES300T have 16, 32 and 40 digital inputs respectively, with matching transistor output counts. See Derell PLCs and smart relays for compact panel applications.
Delta DVP-ES3 · DVP expansion modules · Delta DVP PLC series · Used Delta PLCs · Delta Automation
Manuals and wiring diagrams
External references · Delta ES3 hardware and operation manual · Delta ES3 programming manual · 2024 ES3 instruction sheet in English and Turkish