Delta DVP30EX200T
Delta DVP30EX200T – 30EX2 compact PLC with NPN outputs
Delta DVP30EX200T is a DVP-EX2 series CPU powered by 100–240 V AC at 50/60 Hz. It has 16 digital inputs, 10 NPN transistor outputs, 3 analog inputs and 1 analog output. On a pump panel, it can monitor switches, read a pressure transmitter and a Pt100 sensor, and send an analog speed reference to the drive.
Digital inputs and NPN output wiring
X0–X17 are 24 V DC inputs with octal addressing. Delta specifies 100 kHz for X0–X3, 10 kHz for X4–X7 and 60 Hz for X10–X17 in the input table. Wire the S/S common according to the PNP or NPN sensor diagram. For a high-speed counter, check the limits for the encoder’s A/B phases and the selected counter mode.
Y0–Y11 are sinking NPN outputs. Delta lists 100 kHz for Y0 and Y2, 10 kHz for Y1 and Y3, and 1 kHz for Y4–Y11. Load voltage is 5–30 V DC and the resistive load rating is 0.5 A per output and 4 A per ZP. UP and ZP require an external 24 V DC auxiliary supply. Match the PLC output voltage and current to the stepper or servo drive pulse input.
Analog channels, temperature and 4–20 mA scaling
AD0–AD2 read ±10 V, ±5 V, 1–5 V, ±20 mA or 4–20 mA analog signals with 16-bit A/D conversion. They also support 2- or 3-wire Pt100, Pt1000, Ni100 and Ni1000 sensors. DA0 provides ±10 V, 0–20 mA or 4–20 mA with 12-bit D/A conversion. Match the signal range and the analog I/O wiring to each device.
D1115 sets the channel modes. Its hexadecimal digits represent DA0, AD2, AD1 and AD0 from left to right. In a standalone bench test, HFFFC enables only AD0 in 4–20 mA mode. Read the inputs at D1110–D1112 and the channel status at D1113. Write the DA0 command to D1116. The nominal raw range in 4–20 mA mode is 0–32,000. With a 0–10 bar sensor, 12 mA corresponds to about 16,000 counts and 5 bar. Scale the measurement to engineering units before using it in a PID loop.
Programming software and cable
Use WPLSoft or ISPSoft and select a DVP-EX2 target. Set up the ISPSoft connection in COMMGR. The UC-PRG020-12A connects a PC USB port to the PLC’s COM1 RS-232 8-pin mini-DIN port. Use the UC-MS010-02A with a native RS-232 port. See Delta DVP programming cables for other options.
COM2 and COM3 are RS-485 ports for networks with drives and meters. Match the station address, baud rate and parity on a Modbus RTU network. Check the signal ground and termination against the RS-485 wiring diagram.
Editor’s Note
Check the label and the terminals together. The DVP30EX200T has UP and ZP terminals. The DVP30EX200R has relay commons. When buying a used unit, ask for photos of the front label and the terminal block.
Test the output under load. The Y LED and PLC monitor show the command. Use a suitable 24 V DC test load and a multimeter to confirm switching. Use an oscilloscope to check pulse outputs on Y0 and Y2.
Test the full 4–20 mA loop. Check for readings of approximately 0, 16,000 and 32,000 at 4, 12 and 20 mA. Follow Delta’s jumper diagram for the selected channel’s L+ and I+ terminals. For AD0, the pair is L0+ and I0+.
Test the temperature input separately. Match the sensor and its 2- or 3-wire connection to D1115. At a known temperature of 25.0 °C, expect a raw value of about 250. Check the relevant D1113 status field if the sensor is disconnected.
Back up the project before replacement. With the machine in a safe state, save the project, D1115 settings and serial port parameters. When migrating from a 20EX2 with four analog inputs and two analog outputs, review the channel assignments and scaling for the 30EX2.