The Delta DVP20EX200T is a Delta DVP-EX2 PLC base unit with a 100–240 V AC supply. It has 8 digital inputs, 6 transistor outputs, 4 analog inputs and 2 analog outputs. The digital inputs are 24 V DC sink/source inputs. The transistor outputs switch DC loads. The 100–240 V AC rating applies to the PLC’s main power supply.
Digital inputs and pulse outputs
When wiring PNP or NPN sensors, use the S/S input common as shown on the panel drawing. Follow the 20EX2-T wiring diagram for the UP/ZP auxiliary supply and output loads. Delta’s instruction sheet rates Y0 and Y2 at up to 100 kHz and Y1 and Y3 at up to 10 kHz. For a pulse-controlled servo drive, check both the selected output’s maximum frequency and the electrical type of the drive input.
12-bit analog I/O and scaling
The analog inputs accept ±10 V, ±20 mA or 4–20 mA. The analog outputs provide ±10 V, 0–20 mA or 4–20 mA. Delta’s 20EX2 instruction sheet specifies firmware V1.2 or later for 4–20 mA mode. D1115 selects the channel mode. D1110–D1113 hold analog input values. D1116 and D1117 hold analog output commands.
For example, with a 0–10 bar pressure transmitter in 4–20 mA mode, the PLC reads 0 at 4 mA, 1000 at 12 mA and 2000 at 20 mA. Those values scale to 0, 5 and 10 bar. A 0–10 V reference to a variable-frequency drive uses the positive half of the ±10 V output range. A 4–20 mA analog output uses 0–4000 command counts. Check the analog input and output scales separately in the ladder program.
Programming software, cable and communications
Use WPLSoft or ISPSoft to program the PLC. Select a CPU type that supports DVP-EX2 in the project. The PC connects through the COM1 RS-232 port. Delta’s 2025 manual recommends the UC-MS030-01A cable, with DB9 on the PC side and 8-pin mini-DIN on the PLC side. The older manual lists DVPACAB2A30 for the same connection. COM2 and COM3 can be used for RS-485 Modbus ASCII/RTU. In COMMGR, match the COM port number and serial parameters to the PLC’s current settings.
Editor’s Note
If the nameplate ends in T, check UP/ZP and the load wiring before transferring cables from a panel wired for relay outputs.
For a used unit, disconnect power and inspect L/N, S/S and the analog terminals. Check for loose screws and signs of overheating.
On the bench, test each analog input with a known signal. At 4, 12 and 20 mA you can check zero, midpoint and full scale.
Measure each output in the selected current or voltage mode with a suitable load. On servo applications, check the pulse output at the operating frequency.
Before replacement, back up the program, the D1115 setting, the analog channel scales and the serial settings for each COM port.
Related models and topics
The DVP20EX200R has the same I/O counts with relay outputs. The DVP30EX200R and DVP30EX200T provide more digital I/O and a 3 AI / 1 AO analog configuration. The DVP20SX211T is a 24 V DC slim PLC. For a new panel, assess the Derell Series B PLCs against the project’s I/O and software requirements.
Used Delta automation equipment · Delta PLC · Delta DVP PLC series · Delta DVP PLC files