The Delta DVP30EX200R is a 100–240 V AC DVP-EX2 PLC with 16 digital inputs, 10 relay outputs, 3 configurable analog/RTD inputs and 1 analog output. One CPU can monitor temperature and pressure, switch contactors and send an analog reference to a drive.

Supply, digital inputs and relay terminals

Connect mains power to L–N. The 24 V DC digital inputs are X0–X7 and X10–X17. Wire the S/S common to suit the NPN or PNP sensor. The built-in +24V/24G auxiliary output provides up to 500 mA. The CPU mounts on a 35 mm DIN rail.

C0 is the common for Y0–Y3. C1 is the common for Y4–Y7, Y10 and Y11. Delta rates resistive loads at 2 A per output and 5 A per common. Relay response is approximately 10 ms and maximum switching frequency is 1 Hz. For a contactor or valve coil, check the relay contact life curve for inductive loads and the coil suppression diagram.

Analog inputs, RTDs and registers

AD0–AD2 accept ±10 V, ±5 V, 1–5 V, ±20 mA or 4–20 mA analog signals with 16-bit resolution. Each analog input can also be set for a two- or three-wire Pt100, Pt1000, Ni100 or Ni1000. In RTD mode, the raw unit is 0.1 °C. For example, 250 represents 25.0 °C. See the Pt100 guide and Pt100 vs thermocouple when selecting a sensor.

D1110–D1112 hold the AD0–AD2 readings. D1113 reports channel status. An H2 in the channel’s four-bit field indicates a disconnected RTD. D1115 sets each channel’s signal type. D1062 sets input averaging from 1 to 15 samples.

DA0 is the single analog output. It supports ±10 V, 0–20 mA or 4–20 mA and is commanded through D1116. The 2025 programming manual specifies a command scale of −32000 to +32000 for ±10 V and 0 to 32000 for the current modes on the 12-bit output.

Field example and D1115 setup

In a heating system, AD0 can read a three-wire Pt100 and AD1 can read a 0–10 bar, 4–20 mA pressure transmitter. With AD2 unused and DA0 set to 4–20 mA, D1115 = H2FC4. At 12 mA, AD1 reads about 16000 counts, which represents 5 bar in this example. DA0 can send a drive reference from a PID loop using one of the inputs as feedback. See PID control with a PLC for scaling and control logic.

WPLSoft, ISPSoft and programming cables

Select the CPU profile that covers 30EX2 in WPLSoft or ISPSoft to build the ladder program. Connect the PC to COM1 RS-232. Use UC-PRG020-12A for USB or UC-MS020-01A for a physical PC serial port. Install the USB cable driver and select the correct COM port in the PLC programming software. In ISPSoft, set up the connection through COMMGR. See Delta PLC cables for connector options.

COM2 and COM3 provide RS-485. When connecting an HMI or drive over Modbus RTU, check the station address, baud rate, parity and stop bits. See industrial communication for field network basics.

Editor’s Note

When buying used, check the DVP30EX200R label and confirm the removable analog terminals are included. The T suffix identifies the transistor-output model.

If the Y LED is on and the load stays off, check the relevant C0 or C1 common. Verify the relay contact with a suitable test load and a multimeter.

If an RTD reading looks wrong, check the sensor type in D1115 and the two- or three-wire connection. Read the channel status in D1113.

The 2012 instruction sheet gives a 0–4000 current output command scale. The 2025 programming manual gives 0–32000. When commissioning an older CPU, verify DA0 with a suitable test load while the process load is disabled.

If readings jump when a drive starts, route sensor cables away from motor wiring. Check shield connections, grounding and sources of electromagnetic interference.

Before replacing the CPU, back up the program, retained values and COM settings. On the first test, check each input and output against its field label.

Related models and pages

The DVP30EX200T is the transistor-output 30EX2 model. The DVP20EX200R and DVP20EX200T are 20EX2 models with 4 AI and 2 AO. The DVP20SX211T is a 24 V DC SX2 option. See Derell PLCs and smart relays for compact panel applications.

Delta DVP-EX2 · DVP expansion modules · Delta DVP PLC series · Used Delta PLCs · Delta Automation

Manuals and wiring diagrams

Delta DVP PLC files

External references · DVP30EX2 instruction sheet, 2014 · DVP30EX2 instruction sheet, 2012 · Delta programming manual, analog registers · Delta ES2/EX2 cable selection diagram