Delta DVP20EX200R
Delta DVP20EX200R PLC with analog I/O and relay outputs
The Delta DVP20EX200R is a 100–240 V AC PLC in the DVP-EX2 series with a 16,000-step program capacity. It has 8 digital inputs, 6 relay outputs, 4 analog inputs and 2 analog outputs. The built-in analog I/O can read a pressure transmitter and send a reference to a drive, or be used for level control and PLC-based PID control.
Digital inputs and relay commons
X0–X7 are 24 V DC digital inputs. The S/S common is wired for sink or source operation as required. Y0–Y3 share C0 and Y4–Y5 share C1. Delta specifies 2 A per point and 5 A per common for resistive loads. For coils and other inductive loads, use the manual’s load limits and relay contact life curves. Check the PLC I/O functions and the differences between analog and digital inputs when moving wiring.
12-bit analog channels and scaling
AD0–AD3 support −10 to +10 V, −20 to +20 mA and 4–20 mA. DA0–DA1 support −10 to +10 V, 0–20 mA and 4–20 mA. Select each analog input and output mode in D1115. Delta’s programming manual specifies a nominal 4–20 mA raw range of 0–2000 for input and 0–4000 for output. The Turkish hardware guide specifies V1.2 or later CPU firmware for this mode.
Read input values from D1110–D1113 and write output commands to D1116–D1117. Use the sensor’s measuring range to scale the analog signal to bar, litres or percent. Verify the PID feedback and output reference scales individually.
Programming software and cables
Use WPLSoft or ISPSoft for ladder programming. For ISPSoft, select the PC COM port in COMMGR. COM1 is the 8-pin mini-DIN RS-232 programming port. Use UC-PRG020-12A for USB or UC-MS020-01A for a PC with DB9 RS-232. Delta’s programming manual also gives the COM1 pinout for the UC-MS030-01A.
COM2 and COM3 are RS-485 ports. For HMI or drive communication, match the Modbus ASCII or Modbus RTU settings to the connected device. Check the differences between RS-232 and RS-485 when selecting a cable.
Editor’s Note
On a used unit, start by checking the 200R suffix and the AC supply rating on the label. Make sure the terminal covers and removable blocks come with the PLC.
Back up the project when you connect. Record the analog channel modes in D1115 and the scaling values in the project.
A relay click alone tells you little about the contact. With the load circuit disconnected, use a multimeter to verify that the contacts in the C0 and C1 groups open and close.
Apply a known test current to each analog input, then measure DA0 and DA1 individually. In 4–20 mA mode, the 12 mA midpoint is approximately 1000 on the input and 2000 for the output command.
If a reading drifts, check the V/I terminals, analog common, shielding and grounding. A nearby drive power cable can introduce electromagnetic interference into the signal line.
PDF manuals
Delta DVP PLC files · ES2/20EX2 instruction sheet (EN/Chinese) · ES2/20EX2 hardware guide (Turkish)
Related topics and models
DVP20EX200T is the transistor-output 20EX2 model. DVP30EX200R and DVP30EX200T use a different digital terminal layout and have 3 analog inputs and 1 analog output. DVP20SX211R is a 24 V DC SX2 model with a similar analog channel count.
DVP20EX200R · DVP-EX2 · Delta DVP PLC series · Delta PLC · Used Delta automation
External references
Delta programming manual (EN) · Delta PLC/HMI cable selection guide (EN)