Delta DVP28SV11S2 — SV2 PLC with 16 inputs and 12 PNP outputs

The Delta DVP28SV11S2 is a 24 V DC PLC with 16 digital inputs and 12 PNP transistor outputs in the DVP-SV2 family. It provides 30,000 program steps. Inputs X0–X17 and outputs Y0–Y13 are numbered in octal. Mount DVP expansion modules on the right and compatible high-speed or communication modules on the left.

The PLC can command a pulse-input servo or stepper motor drive in cutting and feed equipment. Check the drive’s pulse input voltage, optocoupler input current and common connection. Use a compatible interface if an input requires a differential line driver. For position feedback, match the encoder’s electrical output to the PLC’s high-speed counter configuration.

PNP output groups and high-speed pulses

Y0–Y7 use UP0/ZP0, and Y10–Y13 use UP1/ZP1. Connect UP to +24 V DC and ZP to 0 V in the group in use. Wire the load between the relevant Y terminal and 0 V. When on, the output supplies positive voltage to the load. Connect the single S/S input common to +24 V DC for NPN sensors or 0 V for PNP sensors. See the NPN and PNP and sink/source guides for current direction.

Delta specifies 0.3 A per output at 40 °C for resistive loads. For a DC-coil interface relay, check coil current and the manufacturer’s surge suppression guidance. Y0, Y2, Y4 and Y6 are the four axis pulse points. With suitable instructions and wiring, each axis supports up to 200 kHz. Delta lists X0, X1, X4 and X5 in the 200 kHz input group. Check the encoder counting limit for the selected counting mode.

Programming software, cable and communication

Use WPLSoft or ISPSoft for PLC programming and select the SV2 CPU family. With ISPSoft, configure the serial port in COMMGR. The Delta cable guide lists the UC-PRG020-12A USB programming cable for COM1 RS-232. Check the COM number assigned by the computer. The guide also lists the UC-MS010-02A and other DVP programming cables for serial connection.

COM2 RS-485 connects to field devices using Modbus RTU. Delta’s cable guide shows the IFD6500 for a PC connection over RS-485. Projects requiring Ethernet can use the DVPEN01-SL left-side expansion module.

Editor’s Note

When buying used, check the S2 nameplate suffix and the UP/ZP terminals. The T2 uses NPN outputs with C-group commons. Compare the wiring diagrams before transferring the harness.

Back up the PLC program and any required retained D values. If BAT.LOW is lit, check the battery and retained data.

If the output LED is on and the load stays idle, measure the 24 V DC supply at that group’s UP/ZP pair. Check the separate supply connection for the second group as well.

Prevent mechanical movement during the initial pulse test. Start at low frequency and check the pulse and direction signals at the drive input.

When troubleshooting an input or output, monitor the PLC I/O state, then check the terminal and common with a multimeter.

Related topics and PLCs

DVP28SV11T2 16 inputs and 12 NPN outputs · DVP28SV11R2 16 inputs and 12 relay outputs · DVP24SV11T2 10 digital inputs and 2 analog inputs · DVP28SV11T earlier SV NPN model

Delta DVP PLC series · Used Delta PLCs · Delta main page

PDF files and manuals

Delta DVP PLC PDF files

External references · Delta DVP-SV/SV2 installation and wiring sheet (includes EN) · Delta PLC/HMI Cable Selection Guide, section 1.7 (EN) · Delta DVP Application Manual for Programming (EN)