Delta DVP28SV11R2

Delta DVP28SV11R2 SV2 PLC with 16 Inputs and 12 Relay Outputs

The Delta DVP28SV11R2 is a compact 24 V DC PLC in the DVP-SV2 series. It has 16 digital inputs, 12 mechanical relay outputs and 30K steps of program memory. It can read sensors and sequence valves, contactors and indicators on packaging, sorting and filling machines.

On a sorting line, a photoelectric sensor can detect an incoming product while an encoder tracks how far the belt has moved. When the product reaches the sorting point, the PLC can command a pneumatic valve through a relay contact. The encoder pulse rate determines the input choice, and the valve switching frequency determines the output choice. For motor circuits, consider the load and coil requirements when selecting a contactor.

Power supply, digital inputs and relay outputs

Supply • The CPU operates at a nominal 24 V DC, with a supply range of 20.4–28.8 V DC and a power consumption of 6 W. When sizing the 24 V DC power supply, account for startup current, expansion modules and field devices sharing the supply.

Inputs • The 24 V DC inputs are addressed X0–X7 and X10–X17. Connect the S/S common to 0 V for PNP sensors and to +24 V for NPN sensors. X0, X1, X4 and X5 are among the high-speed inputs available for encoder pulses. For 200 kHz operation on X10, X11, X14 and X15, check Delta’s requirement for a hardware revision later than A2.

Outputs • The relay outputs are addressed Y0–Y7 and Y10–Y13 with C0–C3 common groups. Delta specifies 1.5 A per output and 5 A per common group for resistive loads, with a maximum switching frequency of 1 Hz. The specified working voltage is 250 V AC or below 30 V DC. Consider the inductive load characteristics and suitable suppression for contactor and valve coils. For high-speed pulse commands to servo or stepper drives, review the transistor-output SV2 models.

Expansion • Compatible DVP expansion modules connect on the right, and supported high-speed modules connect on the left. To read a pressure or level transmitter, add a DVP Slim analog input module that matches the signal range.

WPLSoft, ISPSoft and programming cable

Use WPLSoft to write ladder logic, transfer programs and monitor I/O online. In ISPSoft, select the DVP-SV2 CPU family and configure the serial connection in COMMGR. Keep the original project file if you need to convert it for another programming tool.

Delta lists the UC-PRG020-12A for the DVP28SV11R2. This Delta programming cable connects the PC’s USB-A port to the CPU’s COM1 RS-232 port through its 8-pin mini-DIN plug. Once the driver is installed, select the COM number assigned by Windows. COM2 RS-485 can connect to an HMI, drive or instrument using Modbus. Compare station address, baud rate, parity and protocol settings at both ends.

Editor’s Note

When buying a used CPU, look for the R2 suffix on the nameplate. The front-panel LEDs may look the same across generations. Ask for clear photos of the power plug and expansion connectors.

Before a machine retrofit, save the program, serial settings and module order. When moving from an original SV CPU, check the project settings and the exact module codes even when the I/O count matches.

If a whole output group fails, start with the supply at the group’s C terminal and its fuse. If one relay output is intermittent, isolate the supply before checking contact continuity with a multimeter.

If the programming connection fails, find the cable’s COM number in Windows Device Manager. Select the same number in WPLSoft or COMMGR and check that the cable is plugged into CPU COM1.

If encoder counts become erratic when the drive starts, check the input assignment, sensor supply, cable shield and grounding. Routing the encoder cable in the same duct as power wiring can increase electromagnetic interference.

Related PLC models

DVP28SV11R • Original SV with relay outputs and 16K steps of memory. DVP28SV11T2 • SV2 with NPN transistor outputs. DVP28SV11S2 • SV2 with PNP transistor outputs. DVP24SV11T2 • Ten digital inputs, twelve NPN outputs and two analog inputs. For a new panel, you can also review Derell B Series PLCs against your I/O and communication requirements.