Delta DVP24SV11T2
Delta DVP24SV11T2 PLC – 10 Digital Inputs, 12 NPN Outputs and 2 Analog Inputs
The Delta DVP24SV11T2 is a compact PLC CPU in the Delta DVP-SV2 series. It runs on 24 V DC and provides 30K steps of program memory, 10 digital inputs, 12 NPN transistor outputs and 2 built-in analog inputs. The same CPU can read a pressure or level signal directly and handle machine positioning and discrete control.
Digital inputs, NPN outputs and motion control
The 24 V DC digital inputs are addressed as X0–X7 and X10–X11. Wire the S/S common to suit the sensor output type. The PNP and NPN sensor guide explains the input wiring. The Y outputs are NPN open-collector outputs that sink load current. Check the model's terminal diagram for the C0–C4 common groups.
Delta specifies maximum switching frequencies of 200 kHz for Y0–Y4 and Y6, and 10 kHz for Y5, Y7 and Y10–Y13. The PLC instruction determines which pulse/direction pair and axis count you can use. Check the pulse input and electrical interface of the servo or stepper motor drive before wiring it. For feedback, high-speed counter input limits depend on the channel and hardware revision. See PLC high-speed pulse outputs for more on selecting outputs.
Built-in analog inputs and PLC registers
AD0 and AD1 support 0–10 V / 0–4000 / 12-bit in voltage mode and 0–20 mA / 0–2000 / 11-bit in current mode. Follow the channel diagram in the instruction sheet when wiring voltage or current. For example, a 4–20 mA pressure transmitter gives nominal raw values of 400–2000. Scale these counts to the range on the transmitter label. The guides to analog inputs and 0–10 V and 4–20 mA signals explain wiring and scaling.
D1115 sets the channel mode. Bits 0–3 control AD0 and bits 4–7 control AD1. Within each four-bit field, 0 means voltage, 1 means current and F means off. The factory setting is HFFFF. Read D1110 for AD0 and D1111 for AD1. D1062 sets the number of samples to average (1–20), and D1118 sets the sampling time. An averaging count of 1 returns the current reading.
Programming software, cable and communications
Use WPLSoft or ISPSoft and select the CPU type for the DVP-SV2. To read or download a program from a PC, connect the UC-PRG020-12A USB-to-RS-232 cable to the CPU’s 8-pin mini-DIN COM1 RS-232 port. After installing the driver, select the Windows COM port in WPLSoft or in COMMGR for ISPSoft. See Delta DVP programming cables for other connection options.
The COM2 RS-485 port supports Modbus serial communications. For Ethernet projects, the DVPEN01-SL can connect to the left-side high-speed expansion bus. Use standard right-side DVP expansion modules to add digital and analog I/O.
Editor’s Note
When buying a used CPU, read the label and verify the complete model code. Before a bench test, inspect the analog terminals, removable power plug and COM1 connector.
Back up the source project, communications settings and analog scaling before replacing a CPU. Verify the link and input readings with the output loads disabled.
If an analog value stays fixed, check that the channel is enabled in D1115 and that its mode matches the terminal wiring.
For a current input test, use a signal source to apply 4, 12 and 20 mA. The nominal readings are 400, 1200 and 2000, respectively.
For positioning, verify direction and pulse count at low speed first. An output LED can light even when the drive receives an incorrect pulse signal.
Related models and files
The DVP28SV11T2 has 16 digital inputs and 12 NPN outputs. The DVP28SV11R2 has relay outputs, and the DVP28SV11S2 has PNP transistor outputs. The DVP24SV11T2 is the model in this group with built-in AD0 and AD1. For a project that needs built-in analog I/O, compare the I/O and pulse specifications of the DVP-SX2 family as well.
Delta DVP PLC series · Delta PLC models · Used Delta automation equipment · Delta DVP PLC PDF files
External references · Delta DVP-SV2 Installation and Wiring Sheet (2023, EN) · Delta DVP-PLC Application Manual: Programming (2020, EN) · Delta PLC/HMI Cable Selection Guide (2019, EN)