Delta DVP20EH00R3

Delta DVP20EH00R3 – PLC with 12 Inputs and 8 Relay Outputs

The Delta DVP20EH00R3 is a Delta DVP-EH3 PLC CPU powered by 100–240 V AC. It has 12 digital inputs rated at 24 V DC and 8 relay outputs. In machine automation applications such as packaging, material feeding and part counting, it can count fast signals while operating the control circuits for contactors or valves.

Inputs, relay outputs and addressing

The onboard inputs are addressed X0–X13 and the outputs Y0–Y7. Addresses use octal numbering. The first digital expansion inputs start at X20 and outputs at Y20. When wiring an inductive sensor, photoelectric sensor or limit switch, check the signal level and the S/S input common. PNP and NPN sensors require different common wiring. For continuous measurements, see how analog and digital inputs differ.

For resistive loads, Delta rates the relay contacts at 2 A per output and 5 A per common. When switching a coil, allow for inrush current and use suitable transient suppression. Check the panel schematic for fuse protection and protective grounding. Review the emergency-stop function as part of the machine’s safety circuit.

Two 200 kHz counter channels and one 20 kHz channel

The high-speed input pairs X0/X1 and X4/X5 are rated up to 200 kHz, and X10/X11 is rated up to 20 kHz. With an incremental encoder, check the A/B channel order, signal level and counting mode. For a differential line-driver encoder, use the input schematic to determine the required interface. If count errors increase when the motor starts, check for electromagnetic interference and review the signal cable routing.

Programming software, cable and serial communication

Use WPLSoft or ISPSoft for PLC programming. Select DVP-EH3 as the project target. Read and save the existing ladder program before making changes. In ISPSoft, configure the serial connection profile through COMMGR.

Connect to COM1 (RS-232) for programming. Use UC-PRG020-12A with a USB-equipped PC or UC-MS030-01A with a PC that has a physical RS-232 port. Install the USB cable driver and select the COM number shown in Windows. See Delta PLC cables for other options.

COM2 (RS-485) supports industrial communication. On an existing RS-485 Modbus link, record the station number, baud rate, parity and protocol mode. For a Modbus RTU connection to SCADA, read a known address after replacing the CPU to verify data flow.

Editor’s Note

Check the suffix on the label. When buying used, ask for the complete DVP20EH00R3 code and a close-up of the terminals. R3 and T3 units use different output wiring.

Back up the program first. With the machine in a safe state, save the existing program, communication settings and module order.

Test the relays under load. With the Y LED on, verify that the contact switches a suitable test load. Cycle frequently used outputs several times.

Test the counters separately. Monitor the input pair in use with a suitable test signal. Check the 20 kHz limit if the project uses X10/X11.

Compare addresses on the replacement CPU. Match the first expansion block’s X20/Y20 addresses against the old project’s I/O list.

Related Delta models

The DVP20EH00T3 has the same 12 inputs and 8 outputs. Its transistor outputs can generate pulses up to 200 kHz on two axes. The relay-output DVP16EH00R3 has 8 inputs and 8 outputs, the DVP32EH00R3 has 16 inputs and 16 outputs, and the DVP40EH00R3 has 24 inputs and 16 outputs. Compare field terminals and program addresses before replacing the CPU.

Internal references and PDF files

Delta DVP PLC PDF files · Delta DVP PLC series · Used Delta products

External references

Delta DVP-EH3 installation and wiring sheet (PDF) · Delta DVP PLC programming manual (PDF) · Delta PLC/HMI cable selection guide, section 1.10 (PDF) · Delta DVP-EH3 product page