Delta DVP40EH00R3

Delta DVP40EH00R3 – PLC with 24 inputs and 16 relay outputs

The Delta DVP40EH00R3 is a Delta DVP-EH3 PLC CPU with a 100–240 V AC supply, 24 digital inputs at 24 V DC (X0–X27) and 16 relay outputs (Y0–Y17). X and Y addresses use octal numbering. Delta lists 30K program steps and 12K words of data registers. Typical duties include station sequencing, part counting and auxiliary load control in packaging and assembly machines.

Inputs, high-speed counting and relay loads

Check the AC supply to the CPU and the 24 V DC input circuit separately. Match the S/S common to the PNP or NPN sensor and follow Delta’s diagram for the required sink/source arrangement. An inductive sensor can detect a metal part, a photoelectric sensor can detect passing products and a limit switch can report end-of-travel. Match the NO/NC contact action to the program condition.

In the appropriate counting mode, X0/X1, X4/X5, X10/X11 and X14/X15 are 200 kHz-class high-speed input pairs. Check the encoder’s A/B phases, output circuit and actual pulse rate. Use a compatible expansion module for an analog input such as 0–10 V or 4–20 mA.

Delta rates the relay outputs at 2 A per point and 5 A per common for resistive loads. For contactor or solenoid coils, check inrush current, suppression and fuse selection. Follow the panel’s protective grounding requirements and route signal wiring away from power cables.

Programming software and cable

Program the controller with Delta WPLSoft or Delta ISPSoft. When programming the PLC, select the EH3 CPU target and check the existing ladder diagram instructions against the installed firmware. For ISPSoft, start the RS-232 channel in COMMGR and select that channel in ISPSoft.

For a USB-equipped PC, use the UC-PRG020-12A converter cable. Plug its mini-DIN end into the PLC’s COM1 RS-232 port. Install the Windows driver and select the assigned COM number. The UC-MS020-01A cable suits a PC with a physical serial port. See Delta PLC programming cables for connection options.

Communication and related Delta models

COM2 is the RS-485 port. On a Modbus RS-485 network, match station addresses, baud rate and serial framing. Check Modbus RTU settings against the existing project. The RS-232, RS-422 and RS-485 comparison and industrial communication guide explain the interface choices. COM3 requires a compatible serial function card. For Ethernet, use the DVP-FEN01 card with supported CPU firmware.

The DVP40EH00T3 offers the same 24 inputs and 16 outputs, with transistor outputs. For high-speed pulse commands to a servo or stepper drive, check the T3 pulse outputs and drive interface. The DVP48EH00R3 offers 24 inputs and 24 relay outputs, and the DVP64EH00R3 offers 32 inputs and 32 relay outputs.

Editor’s Note

Ask for the nameplate first when buying used. The photo should show the full model, AC supply rating and any installed card label. Check output commons for heat marks or loose terminals.

Back up the machine before removing the CPU. Save the program, retained data, serial settings and any Ethernet card configuration.

A relay can click even when its contact fails under load. Isolate power and inspect the terminals. With machine loads disconnected, test each output using a suitable test load. See the electrical measurement and test guide.

Test the encoder at operating speed. Check A/B direction and counting consistency as speed increases.

Test COM1 and COM2 separately. Read the PLC program through COM1 and verify data exchange with an RS-485 field device through COM2.

Internal references and PDF files

Delta DVP PLC PDF files · Delta DVP-EH3 series · Delta DVP PLC series

External references

Delta DVP-EH3 hardware and terminal instruction sheet · Delta DVP Application Manual · Delta DVP product catalogue · Delta PLC/HMI Cable Selection Guide (§1.10.1) · Delta DVP-FEN01 instruction sheet · Delta ISPSoft User Manual